Figure 3-9 
IT Rack and Conduit Grounding Connections 
Rear
Emerson Network Power
DCM IT Rack
Ground Bar
(1/4-20 Captive Nuts
on 5/8
” Centers)
(Recommended Torque:
84 in-lbs [9 Nm])
To
Site
Ground
To IT Rack
Frame Ground
Suggested
Connection
Points
To Sub-Rack(s)
Grounding Stud
To HRMG Ground
(if required)
To NPG Ground
(if required)
Conduit Grounding Points
(Stripped Wire Type Connection)
(Wire Size Capacity: see below)
(Recommended Torque: see below)
14-10 AWG (2.5-6mm
2
)
20 in-lbs (2 Nm)
8 AWG (10mm
2
)
25 in-lbs (3 Nm)
6-4 AWG (16-25mm
2
)
35 in-lbs (4 Nm)
Load Distribution
Sub-Rack
Front View
(covers removed)