Installation Instructions 
Issue AB, April 3, 2013 
Spec. No. 584000300 (Model 4015-X003) 
 
Page 28 
Chapter 3. Making Electrical Connections 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
AC Input Power Connections 
Danger: 
Adhere to the “Important Safety Instructions” presented at the front of 
this document.  DO NOT attempt to work on an energized system. 
AC input connections are made to an AC input terminal block located behind an access 
panel located on the rear of the power and control sub-rack.  Studs are also provided for 
the AC Input ground leads.  Refer to Figure 3-10 for location and connection details. 
 
 
Figure 3-10 
AC Input Power Connections 
+
+
-
-
Power and Control Sub-Rack
Rectifier Shelf Rear View
(covers removed)
AC Input
Ground Lead
Stud (10-32 x 5/16
”)
(Recommended
Torque: 23 in-lbs
[3 Nm])
A
B
C
AC Input
Nominal 380V/400V/480V AC,
Three-Phase, 50/60 Hz.
(Wire Size Capacity: see below)
(Recommended Torque: see below)
2-3 AWG (35-30mm
2
)
50 in-lbs (5.65 Nm)
4-6 AWG (25-16mm
2
)
45 in-lbs (5.08 Nm)