Emerson 30-200kVA Manuel D’Utilisation

Page de 132
Operator Control Panel and Display
93
8.1.1
Mimic Power Flow
The LED mounted on the mimic flow chart represent the various power paths and current UPS oper-
ational status.
8.1.2
Audible Alarm (Buzzer) 
UPS activity is accompanied by the following sounds
Table 13
Rectifier indicator—1
Green
Rectifier in Normal Operation
Flashing
Green
Input AC Normal, but rectifier not operating
Red
Rectifier Failed
Off
Rectifier Not operating, Input AC Not Available or out of normal range 
Table 14
Battery indicator—2
Green
Battery Normal, but discharging and powering the load
Flashing
Green
Battery End of Discharge pre-warning
Red
Battery abnormal (Failed, Absent or Polarity Reversed) or Battery 
Converter abnormal
(Failed, overcurrent, overtemperature)
Off
Battery and Converter Normal, Battery charging.
Table 15
Bypass indicator—3
Green
Load on Bypass power
Red
Bypass not available, out of normal range or Static bypass switch fault.
Off
Bypass Normal, load not on bypass
Table 16
Inverter indicator—4
Green
Inverter Normal and powering the load
Flashing
Green
Inverter ON, starting up, synchronising, 
or standing by (ECO mode)
Red 
Inverter failed
Off 
Inverter not operating 
Table 17
Load indicator—5
Green
UPS output ON and Normal
Red 
UPS output ON and Overloaded
Off
UPS output OFF.
Table 18
Status (Alarm) indicator—6
Green
Normal Operation
Yellow
UPS Warning e.g. AC Input Failure 
Red 
UPS fault e.g. Fuse or Hardware failure
Table 19
Audible alarm key
Single beep
Direct Access key acknowledgement
One beep
per second
UPS Warning e.g. AC Input Failure
Continuous
beep
Fault e.g. Fuse or Hardware failure