7.1.2 Audible Alarm
An audible alarm will be used in conjunction with the visual indicators to indicate to the user a 
change in UPS operating status. The audible alarm will enunciate as given in Table 9.
7.2
Troubleshooting
In the event of an issue with the UPS, refer to Table 10 to determine the cause and solution. If the 
issue persists, contact Emerson Channel Support.
Table 9
 Audible alarm description
Condition
Alarm
Battery discharge
half-second beep every 10 seconds
Low battery
Two half-second beeps every 5 seconds
UPS fault, load on bypass
1-second beep every 4 seconds
UPS fault, no power to load
Continuous
Overload
half-second beep every half second
Battery replacement
2-second beep every 60 seconds
Battery loss
Continuous
Wiring problem (including line-to-neutral reversal
or a loss of proper grounding for UPS)
Continuous
Bypass reminder
1-second beep every 2 minutes
Table 10
 Troubleshooting
Problem
Cause
Solution
UPS fails to start when the 
On/Alarm Silence/Manual 
Battery Test button is pressed
UPS is short-circuited or overloaded
Ensure UPS is Off. Disconnect all loads and 
ensure nothing is lodged in output receptacles. 
Ensure loads are not defective or shorted 
internally.
Battery indicator is illuminated
UPS not plugged in
UPS is operating from battery mode, ensure 
UPS is securely plugged into the wall 
receptacle.
UPS input protection circuit breaker 
has opened
UPS is operating from battery mode. Save data 
and close applications. Reset UPS input 
breaker, then restart UPS.
Utility power is out of tolerance
UPS is operating from battery mode. Save data 
and close applications. Ensure utility supply 
voltage is within acceptable limits for UPS.
UPS has reduced battery 
backup time
Batteries are not fully charged
Keep UPS plugged in continuously at least 24 
hours to recharge batteries.
UPS is overloaded
Check load level indicator and reduce the load 
on the UPS.
Batteries may not be able to hold a 
full charge due to age
Replace batteries. Contact your local dealer, 
Emerson representative or Emerson Channel 
Support for replacement battery kit.
Fault and Bypass indicators and 
all LED segments of battery 
level indicator are illuminated
UPS overloaded or load is faulty
Check load level indicator and remove non-
essential loads. Recalculate the load and reduce 
number of loads connected to UPS. Check load 
for faults.
Fault and Bypass indicators and 
diagnostic A indicator are 
illuminated
UPS shutdown due to 
overtemperature condition. Load is 
on bypass power
Ensure UPS is not overloaded, ventilation holes 
not blocked, or room ambient temperature is not 
excessive. Wait 30 minutes to allow UPS to cool, 
then restart UPS. If UPS will not restart, contact 
your local dealer, Emerson representative or 
Emerson Channel Support.