34/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
5. Printer 
Set-up 
 
The UPS is capable of communicating to a serial printer, to printout disparate information. 
Please be sure to have a serial printer, that is a printer with a serial RS232 interface. 
This is the only printer-interface supported by the UPS. 
PRINTER SETUP 
Baud=2400  Parity=O 
Bits=8  Handshake=XON
Print All = N
 
metering 
alarms 
parameters 
+
ok
 
Baud Rate 
This parameter controls the baud rate used for data transmission. 
Although different values can be selected, you must select 2400 Baud
which is the only valid parameter. 
 
Parity 
This parameter controls the parity used for data transmission. 
 
Odd (O) even (E) and “no parity” (X) can be selected. 
 
Nevertheless the only valid value is NO PARITY (X). 
 
Bits 
This parameter controls the length of the data word on the serial line during 
data transmission 7 or 8 bits are offered as choice. 
 Please 
select 
8 bits, as this is the only valid value. 
 
Handshake 
This parameter is used to determine the communication protocol used when 
printing. 
 Valid 
values 
are “XON” standing for the XON/XOFF protocol or “NO” 
standing for any protocol. 
 
Print All This 
parameter 
Y/N is used to print all the available information in the 
sequence meteringalarmsuser and service parameters
 
 
Please configure your printer with the following parameters: 2400/8/N (2400 
bits/sec, 8 bits, no parity). 
 
 
 
6. Printer 
commands 
PRINTER CO M M ANDS 
Print M easures 
= N 
Print Alarm s 
= N 
Print Param eters  = N
 
m etering 
alarm s 
param eters 
+
ok
 
Print Measures This 
Y/N parameter is used to print only the measurement data. 
 
Print Alarms This 
Y/N parameter is used to print only the sequence of all 
Alarms/Events. 
 
Print Parameters This 
Y/N parameter is used to print only the list of User and Service 
Parameters 
 
 
After each printing command the corresponding parameter will be set again 
to N