6  Commissioning 
Issue 10/06 
 
MICROMASTER 440 
58 
Operating Instructions (Compact) 
6.4.18.4 DC 
brake 
 
BI: Enabling the DC brake 
This enables DC braking using a signal that was used from an external source. The 
function remains active as long as the external input signal is active. DC braking causes 
the motor to quickly stop by injecting a DC current 
 
⏐f⏐
P0347
f*
i
t
t
t
1
0
f_act
DC braking
0
1
DC braking active
r0053
Bit00
t
f_set
(0:0)
P1230.C
BI: Enable DC brk.
Note: DC brake can be applied in drive states r0002 = 1, 4, 5
 
DC braking current
 (entered in %) 
Defines level of DC current in [%] relative to rated motor current (P0305). 
 
Duration of DC braking
 (entered in s) 
Defines duration for which DC injection braking is to be active following an OFF1 or OFF3 
command. 
 
t
P1234
OFF1/OFF3
ON
t
t
⏐f⏐
P1233
1
tt
P0347
OFF2
DC braking
OFF2
0
1
DC braking active
r0053
Bit00
 
P1230 = ... 
100 %
0 s
 
 
P1232 =... 
 
P1233 =...