6  Commissioning 
Issue 10/06 
 
MICROMASTER 440 
60 
Operating Instructions (Compact) 
6.4.18.6 Dynamic 
braking 
The following settings should always be made: 
¾
  The Vdc_max controller de-activated 
P1240 = 0 
(def.: P1240 = 1) 
¾
  The compound brake de-activated 
P1236 = 0 
(def.: P1236 = 0) 
¾
  Resistor brake activated 
P1237 > 0 
(def.: P1237 = 0) 
 
 
Dynamic braking 
Dynamic braking is activated using parameter P1237 – the nominal (rated) duty cycle as 
well as the switch-in duration of the braking resistor are also defined. 
 0  Inhibited 
  1  Load duty cycle 5 % 
  2  Load duty cycle 10 % 
  3  Load duty cycle 20 % 
  4  Load duty cycle 50 % 
  5  Load duty cycle 100 % 
Using the dynamic brake, the regenerative feedback energy is transferred to the external 
braking resistor using the chopper control (braking chopper); it is converted into thermal 
energy (heat) in this resistor. This dynamic braking allows the drive to be braked in a 
controlled fashion. This function is not available for sizes FX and GX. 
 
Chopper resistor
Chopper
control
B-
=
~
~
B+
=
~
MM4
 
6.4.18.7 Vdc 
controller 
 
Configuration of Vdc controller 
Enables / disables Vdc controller. 
 0  Vdc controller disabled 
 1  Vdc-max controller enabled 
 
P1254 =... 
Auto detect Vdc switch-on levels 
Enables/disables auto-detection of switch-on 
levels for Vdc control functionalities. 
 0  Disabled 
 1  Enabled 
t
t
⏐f⏐
1
-controller active
V
DC_max
t
V
DC
0
r0056 Bit14
r1242
A0911
f
f
act
set
P1237 = ... 
0
 
1
 
1
 
 
P1240 =...