CAUTION! 
 
PROTECT 1. must be disconnected from the 
power supply prior to carrying out the following 
work. 
If large quantities of dust have accumulated, the unit should, as 
a precaution, be cleaned with dry compressed air, in order to 
ensure adequate heat dissipation. 
The intervals at which visual checks should be performed are 
largely determined by the site conditions. 
10.2.2 
Checking the Battery 
Progressive ageing of the battery system can be detected by 
regular capacity checks. Every 6 months, perform 
measurements to compare the achievable standby times, e.g. 
by simulating a mains failure. In this case, the load should 
always have approximately the same capacity demand. Please 
contact our hotline if the time drops drastically compared to the 
previous measurement (see p. 5). 
10.2.3 Fan 
Check 
Regularly check the fans for dust build-up and noticeably 
untypical noise development. Blocked intake openings must be 
cleaned. In the case of unusually loud or uneven running, 
please contact our hotline (see p. 5).