Connecting Alarms
2-6
296-1011-202 Rel. 5.0, Doc. Rev. 02.01 
CVX 600 Hardware Installation Guide
Procedure
To connect alarms to the terminal block, follow these steps:
Step
Action
1
Select the terminals you want to use for the audible or visual alarm.
2
Use a small flat-tip screwdriver to loosen the two terminal screws for each 
alarm device you want to connect. For example, if you want to connect an 
audible alarm for a critical condition, loosen the terminal screws for the 
terminals labeled Crit(ical) and Ret(urn).
3
Use a wire stripper to remove approximately 1/2 inch of insulation from the 
wires.
4
Insert the wires into the terminals and tighten the screws to 1 to 2 in-lb using a 
1/16-inch flat-tip screwdriver.
5
Connect the other end of the wires to the alarm device.
Tighten screws to 
1 to 2 in-lb, using a
1/16-inch flat-tip
screwdriver.
Remove 1/2 inch
of wire insulation.
Connect wires
to alarm device.
CVX-0184C
Tighten screws to 1 to 2 in-lb
using a 1/16-inch flat-tip
screwdriver.
Remove 1/2 inch
of insulation.
Connect wires
to alarm device.