Emerson 200I/48-NT5C05C Manuel D’Utilisation

Page de 62
14   Specifications 
UM5C05C   P0745680   Standard 6.00   October 2001 
Emerson Energy Systems 
2.2. 
Operation specifications and ambient conditions 
Table 3 - Operation specifications of the rectifier 
Output regulation : 
At the output terminals, the voltage is within ±0.5% of 
the set voltage value for all specified input and output 
variations, and within ±1% for any combination of 
specified input, output and ambient conditions. 
Temperature drift : 
Unless otherwise stated, all input and output 
parameters such as input voltage range, output current 
and voltage, current limit, etc. shall not vary more than 
2% over the operating temperature range. 
Output noise and 
ripple : 
• less than 22 dB of random noise on C band at voice 
frequency over the entire operating range of the 
rectifier, including operation in the current limit mode, 
and at low, nominal and high input voltage conditions 
( with or without batteries and measured at the point 
of regulation ) 
• less than 20 mV RMS in any 3 kHz band between 10 
kHz and 20 MHz ( measurements made with or 
without batteries at the output terminals of the 
rectifier and with the rectifier in the local sensing 
mode ) 
• less than 250 mV peak to peak switching voltage 
spikes ( measured differentially with an a 100 MHz 
oscilloscope ) 
Total harmonic 
distortion ( THD ) : 
Less than 5%. 
Efficiency : 
Better than 89% at a nominal input voltage of 350 V ac 
and for an output current ( load ) greater than 80 A. 
Power factor : 
Better than 99% with an output current ( load ) greater 
than 80 A. 
Heat dissipation : 
The maximum heat dissipation is 1420 watts 
( 4846 BTU / hr ) for an output current ( load ) of 200 A  
at –58 V dc ( when the ac input is 330-475 V )  
Electromagnetic 
interference ( EMI ) : 
The NT5C05CA / CB rectifiers when used in the 
rectifier cabinet NT6C43CA / CB ( equipped with the 
ac EMI filter kit NT6C18KB, or the NT5C05CC without 
external EMI filter ) meet the CISPR requirements for 
conducted and radiated EMI as specified in Publication 
22 for Class "A" equipment. 
Reliability: 
The rectifier has an MTBF greater than 120 000 hours 
under normal operating conditions, at 77°F  ( 25°C ) as 
per Telcordia Technologies TR332 method.