Emerson 200I/48-NT5C05C Manuel D’Utilisation

Page de 62
16   Specifications 
UM5C05C   P0745680   Standard 6.00   October 2001 
Emerson Energy Systems 
2.3. 
Mechanical and electrical specifications of a 1200 A cabinet 
Table 5 - Mechanical specifications of the NT6C43CB 1200 A cabinet
 
Height : 
84.00 inches ( 213.36 cm ) 
Depth : 
23.63 inches ( 60.0 cm ) 
Width : 
23.63 inches ( 60.0 cm ) 
Table 6 - Electrical specifications of the NT6C43CB 1200 A cabinet 
Input voltage : 
380 / 415 V ac three phase 
Output voltage : 
–46 V dc to –58 V dc 
Output current : 
1200 A 
2.4. 
Ambient conditions of a 1200 A cabinet 
Table 7 — Ambient conditions for the NT6C43CB 1200 A cabinet 
Operating 
conditions 
The cabinet is designed for use under the following 
ambient conditions. 
Temperature:  0°C to 50°C ( 32°F to 122°F ) 
0° to 40°C ( 32° to 104°F ) with air 
filters 
Humidity:  
0 to 95% RH ( non-condensing ) 
Altitude:  
sea level to 7,000 ft  ( 2,100 m ) 
Storage conditions 
During transportation and storage, the acceptable 
ambient conditions are : 
Temperature:   –55°C ( –67°F ) 
+60°C ( 140°F ) dry heat 
Humidity:  
0 to 95% RH ( non-condensing )