Emerson 200I/48-NT5C05C Manuel D’Utilisation

Page de 62
Installation   23 
Emerson Energy Systems 
Rectifier 200I/48
NT5C05C   Installation and User Manual 
3.5. 
Connecting the dc output terminals to the busbars 
The dc outputs of the rectifier are connected to the busbars as illustrated in 
Figure 5. There are two methods : 
• 
BAT GRD ( + ) of the rectifier connected to the CHG/ DISCH 
GRD busbar and the –48 V of the rectifier connected to the 
CHG BAT busbar 
• 
BAT GRD ( + ) of the rectifier connected to the CHG GRD 
busbar and the -48V of the rectifier connected to the CHG/ 
DISCH BAT busbar 
Figure 5 - Connecting the dc to the busbars with a shunt on the battery side or a shunt on 
the ground side 
RECTIFIER
+
-
BAT GRD
-48V
CHG / DISCH
GRD BUSBAR
CHG BAT
BUSBAR
SHUNT
DISCHARGE
BAT BUSBAR
FUSE
PANEL
+
-
LOAD
SHUNT ON THE BATTERY SIDE
RECTIFIER
+
-
BAT GRD
-48V
CHG GRD
BUSBAR
CHG / DISCH
BAT BUSBAR
SHUNT
DISCHARGE
GRD BUSBAR
+
-
LOAD
FUSE
PANEL
SHUNT ON THE GRD SIDE ( PREFERRED CONFIGURATION )