24   Installation 
UM5C05C   P0745680   Standard 6.00   October 2001 
Emerson Energy Systems 
3.5.1.  Securing the dc output terminals to the busbars in a 1200 A 
cabinet 
For cabinet applications, no dc cabling is required; the output terminals of 
the rectifier are connected directly to the busbars. 
Procedure 3 - Securing the dc output terminals to the busbars of the 
cabinet 
Step Action 
Connect the BAT GRD output terminal of the rectifier to the BR 
busbar, and the –48 V output terminal of the rectifier to the –48 V 
busbar located at the rear of the cabinet. 
Tighten the bolts by applying a torque of 6.5 
±
 0.5 ft-lbs ( 8.5 
±
 
0.5 N-m ). 
end
 
3.5.2.  Running and connecting the dc between busbars and a 
rectifier 
For frame applications, use terminal lug A0361762, supplied with the unit, 
and no. 110 ( 4/0 ) metric cable. 
Procedure 4 - Typical dc cabling in a frame application 
Step Action 
Connect the BAT GRD output terminal of the rectifier to the CHG 
GRD busbar of the power plant. Connect the –48 V output terminal 
of the rectifier to the CHG / DISCH BAT busbar of the power plant 
( see Figure 5 ). 
Apply a torque of 6.5 
±
 0.5 ft-lbs ( 8.5 
±
 0.5 N-m ) on the bolts 
securing the lugs to the rectifier terminals. 
end
 
3.6. 
Connecting ac to the rectifiers 
 
 
WARNING 
Electrical connections should meet standards 
The electrical installation must be carried out by qualified 
personnel and in accordance with local electrical codes.