Emerson 200I/48-NT5C05C Manuel D’Utilisation

Page de 62
45 
Emerson Energy Systems 
Rectifier 200I/48
NT5C05C   Installation and User Manual 
5. Operation 
5.1. Standard 
settings 
The parameters of the NT5C05CA / CB / CC rectifiers are set as indicated 
in Table 15. For different settings refer to User Manual Voltage_level 
entitled Voltage Level Limits for Power Plants, Rectifiers and Controllers. 
Table 15 - Standard settings for the rectifier 
Parameter Setting 
Rectifier float output voltage ( FLOAT )  
52.1 ±0.1 V dc 
Rectifier equalize output voltage 
( EQUALIZE )  
52.8 ±0.1 V dc 
Rectifier high voltage shutdown threshold  
56.5 ±0.1 V dc 
Rectifier output current limit  
205 A ±5 A 
Rectifier start delay  
4 sec 
Low ac input disconnect  
330 ±5 V ac 
Low ac input reconnect  
350 ±5 V ac 
High ac input disconnect  
475 ±5 V ac 
High ac input reconnect  
460 ±5 V ac 
Load sharing method  
Slope