46   Operation 
UM5C05C   P0745680   Standard 6.00   October 2001 
Emerson Energy Systems 
5.2. 
Starting up and adjusting 
Procedure 9 - Starting up the rectifier 
Step Action 
Put the dc circuit breaker to OFF ( 0 position ). Open the sensing 
leads by removing the corresponding RC fuse ( when the rectifier is 
used with a controller ) or by disconnecting the alarm and control 
cable ( when the rectifier is used without a controller ). 
Put the ac circuit breaker in the main ac service panel to ON. 
Put the 25 A, 3Ø, ac circuit breaker of the rectifier being tested to 
ON. The green ac ON LED should light up. 
Note : The output capacitors are precharged automatically when the 
dc cables are connected at the rear of the rectifier. 
Put the meter selector to the VOLT position. The meter will display 
the voltage value to which the rectifier has been adjusted. 
Connect a digital multimeter to test points VOUT+ and VOUT– on 
the front panel. The voltage reading should be within 1% of the 
rectifier meter reading. If not, calibrate it as described in the 
“ Maintenance ” section. 
Determine the system requirements for float, equalize and HVSD 
limits by referring the User Manual Voltage_Level entitled Voltage 
Level Limits for Power Plants, Rectifiers and Controllers
If the factory threshold limits of the rectifier must be verified or 
changed, go to Step 8; otherwise go to Step 14. 
Adjusting the high voltage shutdown ( HVSD ) 
Put the dc circuit breaker to OFF ( O ). 
Turn the HVSD potentiometer fully clockwise. 
10 
Turn the FLT potentiometer slowly clockwise to set the output 
voltage on the display of the rectifier to the required HVSD threshold. 
The EQL / FLT switch and the EQL potentiometer are used if the 
voltage cannot be set with the FLT potentiometer. 
11 
Turn the HVSD potentiometer counterclockwise until the rectifier 
shuts down. 
12 
Turn the FLT potentiometer counterclockwise two turns and put the 
ac breaker to OFF. 
13 
Wait a few seconds for the rectifier to shut down and put the ac 
breaker to ON to reset it. 
continued