3  Commissioning 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions 
 
6SE6400-5CA00-0BP0 
53
 
Changing single digits in Parameter values 
For changing the parameter value rapidly, the single digits of the display can be 
changed by performing the following actions: 
Ensure you are in the parameter value changing level (see "Changing parameters 
with BOP"). 
1. Press    (function button), which causes the right hand digit to blink. 
2.  Change the value of this digit by pressing 
 / 
3. Press    (function button) again causes the next digit to blink. 
4.  Perform steps 2 to 4 until the required value is displayed. 
5. Press 
the   to leave the parameter value changing level. 
NOTES 
The function button may also be used to acknowledge a fault condition 
 
3.3.4.2 
Commissioning with the Advanced Operator Panel (AOP) 
The Advanced Operator Panel (AOP) is available as an 
option. Its advanced features include the following: 
 
 Multilingual clear text display 
 
Upload/download facility for multiple parameter sets 
 
Programmable via PC 
 
Multidrop capability to drive up to 30 MICROMASTER 
4’s 
Please refer to the AOP Manual for details or contact your 
local Siemens sales office for assistance. 
 
3.3.4.3 
Quick commissioning (P0010=1) 
Mechanical and electrical installation of the inverter must be completed before 
running „Quick Commissioning“. 
It is important that the parameter P0010 is used for commissioning and P0003 for 
selecting the parameter level (level). Quick commissioning particularly uses 
parameters concerning the motor data and the acceleration and deceleration times. 
Quick commissioning is ended with P3900. If this parameter is set to 1, it makes 
the required motor calculations and sets all parameters which are not part of the 
quick commissioning to the default values. 
NOTE 
Parameter P0399 = 0 must be set before starting quick commissioning because it 
is not possible to change the motor data in the works default setting. Once quick 
commissioning has been completed, P0399 = 2 must be set.