3  Commissioning 
MICROMASTER 411 & COMBIMASTER 411    Operating Instructions 
 
6SE6400-5CA00-0BP0 
55
 
Motor data for parameterization 
 
Figure 3-7 
Typical Motor Rating Plate Example 
 
NOTICE 
 
P0308 & P0309 are only visible if P0003 ≥ 2. Only one of the parameters is 
shown depending on the settings of P0100. 
 
Changing motor parameters is not possible unless P0010 = 1(factory setting) 
and P0004 = 0 or 3. 
 
Ensure that the inverter is configured correctly to the motor. 
 
 
3.3.4.4 
Reset to Factory default 
To reset all parameters to the factory default settings; the following parameters 
should be set as follows: 
1.  Set P0010 = 30 
2.  Set P0970 = 1 
NOTICE 
1.  The reset process can take up to 3 minutes to complete. 
2.  Refer to Parameter P0399 for description on saving motor data sets while 
performing a reset to the factory defaults.