Channels
Temperature
Temperature input channels monitor RTD or thermocouple temperature sensors inputs for the most 
common ranges. You can also configure severity alarms that can send an email, a syslog message, 
and/or an SNMP trap when an alarm is triggered or cleared; See 
for more information 
about the alarms.
RTD ranges are:
Thermocouple ranges are:
In the following example, a Temperature I/O IOLAN is used to monitor industrial freezer 
temperature sensors, with an alarm set to send a syslog message if the temperature rises above 31
o
 C. 
TCP Port
Specify the TCP port that the I/O channel or serial signal pin will use to 
communicate to the 
Host
.
Default: 0
z
Pt100 a=385 -50 to 150C
z
Pt100 a=392 -50 to 150C
z
Pt1000 a=385 -40 to 160C
z
Pt100 a=385 0 to 100C
z
Pt100 a=392 0 to 100C
z
NiFe604 a=518 -80 to 100C
z
Pt100 a=385 0 to 200C
z
Pt100 a=392 0 to 200C
z
NiFe604 a=518 0 to 100C
z
Pt100 a=385 0 to 400C
z
Pt100 a=392 0 to 400C
z
Pt100 a=385 -200 to 200C
z
Pt100 a=392 -200 to 200C
Note:
IEC RTD 100 ohms.=0.00385
JIS RTD 100 ohms.=0.00392
z
B 500 to 1800C
z
K 0 to 1370C
z
T -100 to 400C
z
E 0 to 1000C
z
R 500 to 1750C
z
J 0 to 760C
z
S 500 to 1750C
IOLAN
pe
rle
Monitoring
Application
Network
Industrial 
Freezers
Temperature I/O
T4