Configuring Modbus
Modbus Serial Port Settings
Modbus Master Settings
When the Modbus Masters is attached to the IOLAN’s serial port, configure that serial port to the 
Modbus Gateway
 profile acting as a Modbus Master. You must configure the Modbus TCP Slaves 
on the TCP/Ethernet side so the IOLAN can properly route messages, using the Modbus Slave’s 
UIDs, to the appropriate TCP-attached devices. 
To configure the Modbus Master on serial port 1, do the following:
1.
Select the 
Modbus Gateway
 profile for serial port 1.
2.
On the 
General
 tab, enable the 
Modbus Master
 parameter.
3.
Click the 
Destination Slave IP Mappings
 button and click the 
Add
 button in the Destination 
Slave IP Mappings window.
4.
Configure the Destination Slave IP Mappings window as follows:
The IOLAN will send a request and expect a response from the Modbus Slave with an IP 
Address of 10.10.10.11 on Port 502 with UID 22 and from the Modbus Slave with and IP 
Address of 10.10.10.12 on Port 502 with UID 23 (remember when 
Type 
is set to 
Host
, the 
IOLAN increments the last octet of the IP address for each UID specified in the range).
EIA-422/485
Network
EIA-232
TCP
Modbus Master
Master Gateway
Modbus Master
Serial
Modbus Slave
 
IP: 10.10.10.11
 
UID: 22
Modbus Slave
 
IP: 10.10.10.12
 
UID: 23
IOLAN
IP: 10.10.10.10
Serial Port 1