INSTALLATION
(continued)
1--3
Functional Test
The Functional Test consists of three checks: manual
operation, voltage checks, and electrical operation.
NOTICE
Do these checks in the order presented to avoid
damaging the automatic transfer switching
equipment.
Read all instructions on the Wiring Diagrams and labels
affixed to the ATS. Note the control features that are
provided and review their operation before proceeding.
1 – Manual Operation
A detachable manual operator handle is provided on the
Transfer Switching device for maintenance purposes only.
Manual operation of the transfer switching device must
be checked before it is operated electrically.
Do not manually operate the transfer switching
device until both power sources are
disconnected: open both circuit breakers.
1. After deenergizing both power sources, open the
enclosure door. Locate and the maintenance
handle on the left side of the transfer switching
device. See Figure 1–6.
2. Grasp the attached maintenance handle and turn it
with thumb and fingers as shown to manually
operate it. The maintenance handle turns the
opposite direction of the weight. Turn it up or down
as shown to manually operate the transfer switching
device. It should operate smoothly without any
binding. If it does not, check for shipping damage
or construction debris.
3. Return the transfer switching device to the N
(normal) position.
Now continue to 2 – Voltage Checks on next page.
maintenance
handle
With
ALL POWER OFF grasp
maintenance handle and turn it
quickly with your thumb and fingers.
weight marked
(normal)
and
(emergency)
floating
weight
weight
Position of the transfer switch is indicated here
Figure 1-6. Maintenance handle and positions.