Emerson 381333234 E Manuel D’Utilisation

Page de 18
INSTALLATION
(continued)
1--5
press this button
observe these lights
Figure 1–8. Standard controls and indicators.
3 – Electrical Operation
This procedure will check the electrical operation of the
Automatic Transfer Switching Equipment.
Close the automatic transfer switching
equipment enclosure door and tighten the
screws before you test electrical operation.
Transfer Test
Both normal and emergency sources must be available
and the emergency source generator (if used) must be
capable of being started in this procedure.
Perform steps 1 through 8 at the right. Observe the status
lights. See Figure 1–8.
O
Black circle means light is on.
P
White circle means light is off.
NOTE: If Motor Load Transfer
feature is activated, then transfer may
not occur immediately after the
respective time delays. Transfer will
only occur when the phase relationship
between sources is correct.
NOTE: The operating transfer time of the transfer
switching device is 0,17 second maximum, which is
measured from the time that power is applied to the
operating coil of the transfer switching device until the
main contacts close on the alternative source.
This completes the Functional Test of the ASCO
Series 200 Automatic Transfer Switching Equipment.
Leave the engine–generator starting control in the
automatic
position.
1
The normal source must be
available and the generator
must be ready to start.
Check that the
Normal Source
Accepted light is on.
Source Accepted
Normal
Emergency
2
Press and hold the
Transfer Test
button until the engine starts
and runs. This should happen
within 15 sec.
Transfer
Test
3 The Emergency Source
Accepted light should come on.
Source Accepted
Normal
Emergency
4
The transfer switching device
should transfer to the
Emergency position. The
Emergency Transfer Switch
Position light should come on
and the
Normal light should go
off.
Transfer Switch
Position
Normal
Emergency
5
If the
transfer to emergency
delay is used the transfer
should occurs after a time delay
(up to 5 minutes).
For immediate transfer press
the
Bypass Time Delay button.
Bypass
Time Delay
6
The transfer switching device
should transfer back to the
Normal position. The
Normal
Transfer Switch Position light
should come on and the
Emergency light should go off.
Transfer Switch
Position
Normal
Emergency
7
If the
retransfer to normal delay
is used the retransfer should
occur after a time delay
(up to 30 minutes).
For immediate retransfer press
the
Bypass Time Delay button.
Bypass
Time Delay
8
The
unloaded running delay
keeps the generator running for
5 minutes (cool–down period).
Then the generator should stop
and the
Emergency Source
Accepted light should go off.
Source Accepted
Normal
Emergency