Metered Rack PDU User Guide
87
Using the Firmware Upgrade Utility
This Firmware Upgrade Utility is part of the firmware upgrade package available on the APC Web site. (Never 
use an Upgrade Utility designated for one product to upgrade the firmware of another product).
Using the Utility for upgrades on Windows systems. 
On any supported Windows operating system, the 
Firmware Upgrade Utility automates the transferring of the firmware modules, in the correct module order
The utility only works with a Rack PDU that has an IPv4 address.
Unzip the downloaded firmware upgrade file and double-click the .exe file. Then enter the IP address, the user 
name, and the password in the dialog fields and click 
Upgrade Now
. You can use the 
Ping
 button to test your 
entered details.
Using the Utility for manual upgrades, primarily on Linux. 
On non-Windows operating systems, the 
Firmware Upgrade Utility extracts the individual firmware modules, but does not upgrade the Rack PDU. See 
“Firmware File Transfer Methods”  for the different upgrade methods after extraction.
To extract the firmware files:
1. After extracting files from the downloaded firmware upgrade file, run the 
Firmware Upgrade Utility
 
(the .exe file).
2. At the prompts, click 
Next
>, and then specify the directory location to which the files will be extracted.
3. When the 
Extraction Complete
 message displays, close the dialog box.
Use FTP or SCP to upgrade one Rack PDU
FTP. 
To use FTP to upgrade a Rack
 PDU 
over the network:
•  The 
Rack PDU
 must be on the network, with its system IP, subnet mask, and default gateway 
configured.
•  The FTP server must be enabled at the 
Rack PDU
To transfer the files (this procedure assumes bootmon does not need upgrading, it is always necessary to 
upgrade the other two though):
2. At a computer on the network, open a command prompt window. Go to the directory that contains the 
firmware files, and list the files:
C:\>cd apc
C:\apc>dir
3. Open an FTP client session:
C:\apc>ftp
 
4. Type
 open 
with the
 IP address 
of the 
Rack PDU
, and press 
E
NTER
. If the 
port
 setting for the FTP 
Server has changed from its default of 
21
, you must use the non-default value in the FTP command.
• For Windows FTP clients, separate a non-default port number from the IP address by a 
space. For example (showing a space before 21000):
ftp> open 150.250.6.10 21000
 
• Some FTP clients require a colon instead before the port number.
5. Log on as Administrator (
apc
 is the default user name and password).
6. Upgrade the AOS. (Always upgrade the AOS before the application module).
ftp> bin
ftp> put apc_hw05_aos_nnn.bin 
(where nnn
 
is the firmware version number)
7. When FTP confirms the transfer, type
 quit 
to close the session.