APC AP8861 Manuel D’Utilisation
Metered Rack PDU User Guide
87
Using the Firmware Upgrade Utility
This Firmware Upgrade Utility is part of the firmware upgrade package available on the APC Web site. (Never
use an Upgrade Utility designated for one product to upgrade the firmware of another product).
use an Upgrade Utility designated for one product to upgrade the firmware of another product).
Using the Utility for upgrades on Windows systems.
On any supported Windows operating system, the
Firmware Upgrade Utility automates the transferring of the firmware modules, in the correct module order.
The utility only works with a Rack PDU that has an IPv4 address.
The utility only works with a Rack PDU that has an IPv4 address.
Unzip the downloaded firmware upgrade file and double-click the .exe file. Then enter the IP address, the user
name, and the password in the dialog fields and click
name, and the password in the dialog fields and click
Upgrade Now
. You can use the
Ping
button to test your
entered details.
Using the Utility for manual upgrades, primarily on Linux.
On non-Windows operating systems, the
Firmware Upgrade Utility extracts the individual firmware modules, but does not upgrade the Rack PDU. See
“Firmware File Transfer Methods” for the different upgrade methods after extraction.
“Firmware File Transfer Methods” for the different upgrade methods after extraction.
To extract the firmware files:
1. After extracting files from the downloaded firmware upgrade file, run the
Firmware Upgrade Utility
(the .exe file).
2. At the prompts, click
Next
>, and then specify the directory location to which the files will be extracted.
3. When the
Extraction Complete
message displays, close the dialog box.
Use FTP or SCP to upgrade one Rack PDU
FTP.
To use FTP to upgrade a Rack
PDU
over the network:
• The
Rack PDU
must be on the network, with its system IP, subnet mask, and default gateway
configured.
• The FTP server must be enabled at the
Rack PDU
To transfer the files (this procedure assumes bootmon does not need upgrading, it is always necessary to
upgrade the other two though):
upgrade the other two though):
2. At a computer on the network, open a command prompt window. Go to the directory that contains the
firmware files, and list the files:
C:\>cd apc
C:\apc>dir
3. Open an FTP client session:
C:\apc>ftp
4. Type
open
with the
IP address
of the
Rack PDU
, and press
E
NTER
. If the
port
setting for the FTP
Server has changed from its default of
21
, you must use the non-default value in the FTP command.
• For Windows FTP clients, separate a non-default port number from the IP address by a
space. For example (showing a space before 21000):
ftp> open 150.250.6.10 21000
• Some FTP clients require a colon instead before the port number.
5. Log on as Administrator (
apc
is the default user name and password).
6. Upgrade the AOS. (Always upgrade the AOS before the application module).
ftp> bin
ftp> put apc_hw05_aos_nnn.bin
(where nnn
is the firmware version number)
7. When FTP confirms the transfer, type
quit
to close the session.