The HART Communicator will 
display this screen reminding 
the user that the loop should be 
removed from automatic control 
before proceeding.  When this has 
been done, the user must press OK 
to continue.
The user is then notified that 
the loop may now be returned 
to automatic control.  After the 
user presses OK the HART 
Communicator returns to the 
Keypad rerange screen.
If the user has changed the unit 
code, he may then modify the range 
values.  He selects the variable that 
he desires to change by using the 
left arrow on the highlighted line.
If the user selects LRV from the 
Keypad rerange screen, the present 
LRV is displayed above the edit 
box, 0.00 in as shown to the left.  
In this example, the user desires 
to change the LRV to 10.0 in and 
must press ENTER after changing 
the edit box to continue with the 
reranging of the transmitter.
The Keypad rerange screen now 
shows the new value selected 
by the user, but the HART 
Communicator has not sent the 
command to the transmitter.  Note 
the SEND label above F2 that 
indicates the need to send the value 
to the transmitter.
If the user selects URV from the 
Keypad rerange screen, the present 
URV is displayed above the edit 
box, 60.00 in as shown to the left.  
In this example, the user desires 
to change the URV to 55.0 in and 
must press ENTER after changing 
the edit box to continue with the 
reranging of the transmitter.
On returning to the Keypad rerange 
screen, the values shown for LRV 
and URV are the changes that the 
user has made.  The user should 
check the difference between the 
URV and LRV and compare this 
value with the Min span listed 
on the menu.  If the difference is 
smaller than the minimum span, the 
transmitter will not accept the new 
range values.  Note that the label 
above F2 is now SEND.  The user 
must press the SEND key for the 
HART Communicator to send the 
new range values to the transmitter. 
The HART Communicator will 
display this screen reminding 
the user that the loop should be 
removed from automatic control 
before proceeding.  When this has 
been done, the user must press OK 
to continue.
The user is then notified that 
the loop may now be returned 
to automatic control.  After the 
user presses OK the HART 
Communicator returns to the 
Keypad rerange screen.
The keypad rerange screen now 
shows the new LRV, URV and Unit 
selected by the user.
Reranging the Transmitter
Setting the Measurement Value for 4mA and 20mA
by Apply Values
If the user desires to set the 4mA 
and 20mA measurement points by 
setting the Level (or Interface) value 
in the vessel, he must select Apply 
values from the Rerange screen.
If the user selects Apply values from 
the Rerange screen, this screen 
will appear reminding the user 
that the loop should be removed 
from automatic control before 
proceeding.  When this has been 
done, the user must press OK to 
continue.