Low Profile – 1600 Advantage Series Service Manual – International
 
 
 
 
 
 
 
 
 
as needed. 
 
 
 
 
Temperature regulation   
If supply voltage is present on the  
 
 
 
 
valve    
 
 
temperature control board at the load 
 
 
 
 
 
 
 
 
terminals #7 and #8, check for voltage 
 
 
 
 
 
 
 
 
at temperature regulation valve. If  
 
 
 
 
 
 
 
 
voltage is present, listen for valve to  
 
 
 
 
 
 
 
 
open and close. Also, check for opens 
 
 
 
 
 
 
 
 
or shorts in the coil. Replace if required. 
Intermittent heating 
 
Thermal overload of 
 
The main fan motors and the burner  
 
 
 
 
main fan and burner 
 
blower motors are equipped with  
 
 
 
 
blower motors           
 
internal thermal protection and will  
 
 
 
 
 
 
 
 
cease to operate if overheating occurs. 
 
 
 
 
 
 
 
 
As the motors overheat and then cool, 
 
 
 
 
 
 
 
 
this will cause the units to cycle on  
 
 
 
 
 
 
 
 
and off intermittently. This may be  
 
 
 
 
 
 
 
 
caused by improper ventilation or lack 
 
 
 
 
 
 
 
 
of preventive maintenance. Also, most   
 
 
 
 
 
 
 
of the problems listed under “Oven  
 
 
 
 
 
 
 
 
will not heat” can cause intermittent 
 
 
 
 
 
 
 
 
failure. 
Conveyor will not run   
Power supply   
 
Check for supply voltage at terminals 
 
 
 
 
 
 
 
 
L1 and L2. If voltage is not present, 
 
 
 
 
 
 
 
 
check breakers. 
 
 
 
 
Fan switch 
 
 
See procedure for checking on page 6. 
 
 
 
 
Fuse, 10 Amp.   
 
Check and/or replace. 
 
 
 
 
Fuse holder 
 
 
Check and/or replace. 
 
 
 
 
Filter E.M.I. 
 
 
Check for supply voltage input to 
 
 
 
 
 
 
 
 
filter. If there is no voltage, trace wiring  
 
 
 
 
 
 
 
 
back to relay. If there is input voltage,  
 
 
 
 
 
 
 
 
check for output voltage. If there is 
 
 
 
 
 
 
 
 
input voltage but no output voltage, 
 
 
 
 
 
 
 
 
replace filter. 
Speed adjustment  
This is a 0 to 10K ohm, 1 turn  
 
 
 
 
potentiometer    
 
potentiometer. With power off, remove 
 
 
 
 
 
 
 
 
the black and white pot leads from the 
 
 
 
 
 
 
 
 
conveyor control board at terminals 
 
 
 
 
 
 
 
 
P1 and P2. Place the meter leads on  
 
 
 
 
 
 
 
 
black lead (P2) and the white lead (P1). 
 
 
 
 
 
 
 
 
Rotating the pot. slowly, from low to 
 
 
 
 
 
 
 
 
high, the meter reading should show  
 
 
 
 
 
 
 
 
an even transition from 0 to 10K ohms 
 
 
 
 
 
 
 
 
±
 5%. There should be no dead or open 
 
 
 
 
 
 
 
 
spots through the one turn of the pot. 
 
 
 
 
 
 
 
 
Check both leads to ground. There  
 
 
 
 
 
 
 
 
should be no continuity to ground. 
 
 
 
 
 
 
 
 
If any of the above fail, replace  
 
 
 
 
 
 
 
 
the potentiometer. 
 
 
 
 
D.C. motor 
 
 
Check for supply voltage input to 
 
 
 
 
control board    
 
the control board at terminals L1 and L2  
 
 
 
 
 
 
 
If not present, check wiring back to  
 
 
 
 
 
 
 
 
the filter. If supply voltage is present, 
 
 
 
 
 
 
 
 
check both fuses on the control board 
 
 
 
 
 
 
 
 
( 8 Amp. line and 1Amp. armature). 
 
 
 
 
 
 
 
 
Check the D.C. voltage output at  
 
 
 
 
 
 
 
 
terminals A+ and A-. If A.C. voltage 
 
 
 
 
 
 
 
 
is at terminals L1 and L2, and no  
 
 
 
 
 
 
 
 
D.C. voltage is present at A+ and A-, 
 
 
 
 
 
 
replace control board. If A.C. voltage is    
 
 
 
 
 
present and D.C. voltage is present but 
 
 
 
 
 
 
the motor will not run, check gear motor 
 
 
 
 
 
 
as follows: 
 
 
 
 
Conveyor 
 
 
If D.C. voltage is present at A+ and A-