Lincoln 1450 Manuel D’Utilisation

Page de 24
Impinger I – 1450 Series Service Manual - Domestic 
5
not running, check for opens, shorts or grounds. 
WITH POWER OFF: Turn motor to check for locked 
rotor. Replace burner blower motor as needed. 
 
Burner transformer 
Check for 120VAC supplied to primary of burner 
transformer. If no voltage is present, trace wiring back 
to centrifugal switch of main fan motor. If voltage is 
present, check for 24VAC supply at transformer 
secondary. If there is primary voltage but no secondary 
voltage, replace burner transformer. 
 
Centrifugal switch of burner 
blower motor 
Check for 24VAC at motor connector, wire #19 (input to 
centrifugal switch) to neutral. If no voltage is present, 
trace wiring back to burner transformer. If voltage is 
present, check for 24VAC at wire #20 (output of 
centrifugal switch) to neutral. If no voltage is present at 
wire #20 and motor is running, replace burner blower 
motor. 
 
Ignition control 
Check for 24VAC supply to the ignition control. If no 
voltage is present, trace wiring back to centrifugal 
switch of burner blower motor. If voltage is present, 
check for 24VAC at pin #3 and ground (pilot valve). 
NOTE: The Honeywell ignition control has a 30 second 
pre-purge (time delay) built in. If voltage is not present, 
replace ignition control. If the pilot valve is energized, 
check to see that the high voltage igniter circuit is also 
energized. To check, disconnect the igniter lead from 
the ignition control.  
 
No pilot flame 
If the ignition control is supplied with 24Vac and the 
pilot valve (internal to valve assembly) and igniter 
circuits are energized, visually check for pilot flame. 
This may be done by opening the small inspection door 
on the end of the burner, or by opening the main oven 
door and looking under the lower finger housings on 
the right side of the oven. If no pilot flame is visible, 
check the pilot shut-off valve. 
 
Pilot shut-off valve 
Check to see that the pilot shut-off valve is open (shut-
off valve is located between valve assembly and 
burner). 
 
Pilot tube 
Check for gas pressure at the pilot tube. Disconnect 
pilot tube at burner and connect a manometer to pilot 
tube. If no gas pressure is present during ignition, 
check for blockage in pilot tube or pilot shut-off valve. If 
these are clear, and there is gas supplied to the oven, 
replace the gas valve. 
 
Pilot orifice 
If there is gas pressure at the pilot tube, check the pilot 
orifice for obstructions. Replace as needed. 
 
Burner igniter 
Check the burner igniter head for any obstructions, also 
check for frayed or broken wire. Check spark gap (gap 
should be .100 to .125 inch). If there is visible damage, 
replace burner igniter. 
 
NOTE: Flame should be    on 
at this time 
 
Pilot flame, but no  
main flame 
Control transformer 
Check for 120VAC supply to the primary of the control 
transformer. If no voltage is present, trace wiring back 
to the oven power switch. If voltage is present, check 
foe 24VAC at the transformer secondary. If there is 
primary voltage, but no secondary voltage, replace 
control transformer.  
 
Oven control 
Check for 24VAC supply to oven control. If no voltage 
is present, trace wiring back to control transformer. If 
24VAC is present, check for a read-out on the display. 
If there is 24VAC supplied, but there is no read-out on