3 Wiring
3.4 Analog Output Wiring
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3U
-4DA (4-channel Analog Output)
3.4
Analog Output Wiring
The analog output mode, "voltage output "or "current output", can be selected for each channel. 
*1.
For FX
3G
/FX
3U
 Series PLC (AC power type), the 24V DC service power supply is also available. 
*2.
Do not connect any wires to the " • " terminal.
*3.
Use a 2-core twisted shield wire for analog output wire, and separate it from other power lines or
inductive lines.
*4.
If there is ripple or noise in the output voltage, connect a capacitor of approximately 0.1 to 0.47
μF 25V
in the vicinity of the signal receiving side. 
*5.
Ground the shielded wire at one point on the signal receiving side.
3.5
Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100
Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following 
figure.
→ For details, refer to the User’s Manual - Hardware Edition of each Series.
• The grounding wire size should be AWG14 (2mm
2
.)
• The grounding point should be close to the PLC, and all grounding wires should be as short as possible.
FX
3U
-4DA
+15V
I+
VI-
V+
24+
24-
-15V
I+
VI-
V+
ch  :   represents the channel number.
ch
Shield *3
24V DC
If voltage output is
selected
If current output is
selected
External power supply
wiring
*1
ch
ch
Class-D grounding
*2
ch
Shield *3
*4
*5
*5
PLC
Other
equipment
PLC
Other
equipment
PLC
Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition