 PLC User's Manual - Analog Control Edition
FX
3U
-4DA (4-channel Analog Output)
4. Analog Output
This chapter describes the minimum programming necessary for analog output by the FX
3U
-4DA. 
Follow the procedure below to confirm that correct analog values can be output.
4.1
Analog Output Procedures
1
Unit number check
Unit numbers from 0 to 7 will be assigned to the special function units/blocks starting from the left.
When the units/blocks are connected to the FX
3UC
-32MT-LT(-2) PLC, the unit numbers from 1 to 7
are assigned. Check the unit number assigned to the FX
3U
-4DA.
2
Output mode (BFM #0) setting
Depending on the analog signal generator to be connected, set the output mode (BFM #0) for each
channel.
Use hexadecimal numbers for output mode setting. Set the corresponding channel digit to the
output mode setting value specified in the following table:
→ For a detailed description of the standard output characteristics, refer to Section 2.4.
→ For a detailed description of the output mode (BFM #0), refer to Subsection 5.4.1.
Setting
value
Output mode
Analog output range
Digital input range
0
Voltage output mode
-10V to +10V
-32000 to +32000
1
Voltage output 
analog value mV specification mode
-10V to +10V
-10000 to +10000
2
Current output mode
0mA to 20mA
0 to 32000
3
Current output mode
4mA to 20mA
0 to 32000
4
Current output 
analog value 
μA specification mode
0mA to 20mA
0 to 20000
F
Channel not used
Main unit
(FX
3U
 Series
PLC)
Input/output
extension
block
Special
function block
Special
function block
Input/output
extension
block
Special
function unit
Unit
number: 0
Unit
number: 1
Unit
number: 2
H
ch4
ch3
ch2
ch1