 PLC User's Manual - Analog Control Edition
FX
3U
-4DA (4-channel Analog Output)
5.4
Buffer Memory Details
5.4.1
BFM #0: Output mode specification
Initial value (at delivery): H0000
Numeric data type: Hexadecimal (H)
Specify the output modes of channel 1 to 4.
4 hexadecimal digits are assigned to specify the output modes of the 4 channels. 
Change the value of each digit to change the output mode of each channel. 0 to 4 and F can be set for each
digit.
The different types of output modes are shown in the following table:
→ For a detailed description of output characteristics, refer to Section 2.4.
*1.
The offset/gain values cannot be changed.
1. Cautions regarding output mode setting
• While the output mode is being changed, the output is stopped, and H0000 is automatically written in the 
output status (BFM #6).
At the completion of change of the output mode, the output status (BFM #6) will automatically change to 
H1111, and the output is restarted.
• It takes approximately 5 seconds to determine the output mode.
For this reason, after changing the output mode, be sure to wait for 5 seconds or more, and then write the 
other data.
• When the output mode is changed, the settings in the following buffer memory are initialized according to 
the new output mode.
BFM #5 (output setting upon PLC stop)
*1
BFM #10 to #13 (offset data)
*2
BFM #14 to #17 (gain data)
*2
BFM #28 (disconnection detection status)
*3
 
BFM #32 to #35 (output data upon PLC stop)
*2
BFM #38 (upper/lower limit function setting)
*1
BFM #41 to #44 (lower limit values of upper/lower limit function)
*2
BFM #45 to #48 (upper limit values of upper/lower limit function)
*2
BFM #50 (Setting of output corrective function by load resistance)
*1
*1 FX
3U
-4DA initializes the corresponding bit to the channel where the user has changed the output mode.
*2 FX
3U
-4DA initializes the corresponding buffer memory to the channel where the user has changed the
output mode.
*3 These settings are initialized only when the output mode is changed from current output mode
(mode 2, 3 or 4) to voltage output mode (mode 0 or 1).
• HFFFF (use of no channels) cannot be set.
Set value
[HEX]
Output mode
Analog output range
Digital input range
0
Voltage output mode
-10V to +10V
-32000 to +32000
1
*1
Voltage output 
analog value mV specification mode
-10V to +10V
-10000 to +10000
2
Current output mode
0mA to 20mA
0 to 32000
3
Current output mode
4mA to 20mA
0 to 32000
4
*1
Current output 
analog value 
μA specification mode
0mA to 20mA
0 to 20000
5 to E
Invalid (setting values unchanged)
-
-
F
Channel not used
H
ch4
ch3
ch2
ch1