Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
E-22
5 Buffer Memory (BFM)
5.4 Buffer Memory Details
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3U
-4DA (4-channel Analog Output)
2. Caution regarding EEPROM writing
If data is written to BFM #0, #5, #10 to #17, #19, #32 to #35, #50 to #54 or #60 to #63, the data will also be
written to the FX
3U
-4DA EEPROM.
Do not turn off the power immediately after writing values in these buffer memories.
The maximum number of EEPROM rewrites is 10,000 times. Therefore, when creating a program, do not
frequently write data to the above buffer memories (BFM).
5.4.2
BFM #1 to #4: Output data
Initial value: K0
Numeric data type: Decimal (K)
Input the digital values corresponding to the analog signals to be output in BFM #1 to #4.
5.4.3
BFM #5: Output setting upon PLC stop
Initial value: H0000
Numeric data type: Hexadecimal (H)
It is possible to set the output conditions from channel 1 to 4 when the PLC is in the stopped state.
* The output conditions depend on the output mode (BFM #0).
1. Cautions regarding output conditions setting upon PLC stop
• While changing the setting values, the output is stopped, and H0000 is automatically written in the output 
status (BFM #6).
At the completion of change, the output status (BFM #6) will automatically change to H1111, and output 
will be restarted.
2. Caution regarding EEPROM writing
• If data is set in BFM #0, #5, #10 to #17, #19, #32 to #35, #50 to #54 or #60 to #63, the data will be written 
in the EEPROM of FX
3U
-4DA.
Do not turn off the power immediately after writing values in these buffer memories.
The maximum number of EEPROM rewritable times is 10,000 times. Therefore, when creating a program, 
do not frequently write data to the above buffer memories (BFM).
BFM number
Description
#1
Data to be output from channel 1
#2
Data to be output from channel 2
#3
Data to be output from channel 3
#4
Data to be output from channel 4
Set value (HEX)
Output conditions
0
The final value during running is held.
1
The offset signal is output.*
2
The output data set in BFM #32 to #35 are output.*
3 to F
Invalid (setting values unchanged)
H
ch4
ch3
ch2
ch1