Mitsubishi Electronics MELSEC-F Manuel D’Utilisation
K-14
3 Wiring
3.4 Selection of the Resistance Thermometer Sensor
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Analog Control Edition
FX
3U
-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)
3.4
Selection of the Resistance Thermometer Sensor
Select the Pt1000/Ni1000 (2-wire or 3-wire sensors) resistance thermometer sensor.
3.5
Wiring of the Resistance Thermomester Sensor
Wiring depends on the resistance thermometer sensor type selected. Refer to the following wiring diagrams:
*1.
24V DC service power supply of the FX
3G
/FX
3U
Series PLC can also be used.
*2.
When using a 2-wire temperature sensor type, short-circuit the [L -] terminal and the [I -] terminal.
For the lead wire use a 10
For the lead wire use a 10
Ω resistance or less per line.
*3.
Separate the cable of the platinum resistance themometer sensor from the other power cables or
areas easily affected by inductive noise (of the commercial power, etc.).
areas easily affected by inductive noise (of the commercial power, etc.).
1M
Ω
ch
PNK-ADP
Class-D grounding
+5V
24+
24-
Shield wire
Terminal
block
24V DC
*1
L
+, L-, I-, ch: represents the channel number.
3-wire
sensors
type
sensors
type
1M
Ω
47k
Ω
47k
Ω
+5V
1M
Ω
ch
+5V
1M
Ω
47k
Ω
47k
Ω
2-wire
sensors
type
sensors
type
L
-
I
-
L
+
L
-
I
-
L
+
*2
*3
Resistance thermometer
wiring
External power supply
wiring