Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
K-14
3 Wiring
3.4 Selection of the Resistance Thermometer Sensor
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3U
-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)
3.4
Selection of the Resistance Thermometer Sensor
Select the Pt1000/Ni1000 (2-wire or 3-wire sensors) resistance thermometer sensor.
3.5
Wiring of  the Resistance Thermomester Sensor
Wiring depends on the resistance thermometer sensor type selected. Refer to the following wiring diagrams:
*1.
24V DC service power supply of the FX
3G
/FX
3U
 Series PLC can also be used.
*2.
When using a 2-wire temperature sensor type, short-circuit the [L† -] terminal and the [I† -] terminal.
For the lead wire use a 10
Ω resistance or less per line.
*3.
Separate the cable of the platinum resistance themometer sensor from the other power cables or
areas easily affected by inductive noise (of the commercial power, etc.).
1M
Ω
ch

PNK-ADP
Class-D grounding
+5V
24+
24-
Shield wire
Terminal
block
24V DC
*1
L
+, L-, I-, ch:  represents the channel number.
3-wire
sensors
type
1M
Ω
47k
Ω
47k
Ω
+5V
1M
Ω
ch

+5V
1M
Ω
47k
Ω
47k
Ω
2-wire
sensors
type
L
-
I
-
L
+
L
-
I
-
L
+
        
*2
*3
Resistance thermometer
wiring
External power supply
wiring