Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
A-32
4 Comparison of Performance Specifications
4.2 Analog Output
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
Common Items
4.2 Analog Output
4.2.4
FX
2N
-4DA
*1.
Adjustment of the offset or gain value will not affect the resolution.
*2.
The offset and the gain should satisfy the following condition:1
1V 
≤ (Gain - Offset) ≤ 15V
*3.
The offset and the gain should satisfy the following condition:
4mA 
≤ (Gain - Offset) ≤ 32mA
Specifications
FX
2N
-
4DA
Voltage output
Current output
Number of output points
4ch
Analog output range
-10V to +10V DC
(External load: 2k to 1M
Ω)
0mA to 20mA DC
4mA to 20mA DC
(External load: 500
Ω or less)
Offset
-5V to +5V
*1,*2
-20mA to +20mA
*1,*3
Gain
15 V or less, and
Gain - Offset 
≥ 1V
32 mA or less, and
Gain - Offset 
≥ 4mA
Digital output
With sign, 12 bits, binary
10 bits, binary
Resolution
5mV(10V
×1/2000)
*1
20
μA(20mA×1/1000)
*1
Overall accuracy
±1.0%(±200mV) for 20V full scale
±1.0%(±200μA) for 20mA full scale
Same accuracy for 4mA to 20mA output
Does not include any load fluctuation.
-
Time required for D/A 
conversion
2.1 ms (The number of selected channels will not affect this value.)
Output characteristics
Insulation method
• The photocoupler is used to insulate the analog input area from the PLC.
• The DC/DC converter is used to insulate the power supply from the analog output.
• Channels are not insulated from each other.
Number of I/O points 
occupied
8 points (Taken from either the input or output points of the PLC.)
0
+2000
+10V
-10V
-2000
z
When the output mode is set to "0":
+2
04
7
-2048
0
1000
Digital input
4mA
A
nal
og
 out
put
20mA
z
When the output mode is "2":
(The dotted line is for mode 1.)
1023