Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
A-33
4 Comparison of Performance Specifications
4.2 Analog Output
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
Common Items
A
C
ommon Item
s
B
FX
3U
-4A
D
FX
3UC
-4A
D
C
FX
3U
-4AD
-A
DP
D
FX
3G
-2A
D
-B
D
E
FX
3U
-4D
A
F
FX
3U
-4DA
-A
DP
G
FX
3G
-1D
A
-B
D
H
FX
3U
-3
A-
AD
P
I
FX
3U
-4A
D
-P
T
   
         
       -
A
D
P
J
FX
3U
-4AD
-P
TW
         
         
 -A
D
P
4.2.5
FX
2NC
-4DA
*1.
Adjustment of the offset or gain value will not affect the resolution.
*2.
The offset and the gain should satisfy the following condition:
1V 
 (Gain - Offset) 
 15V
*3.
The offset and the gain should satisfy the following condition:
4mA 
 (Gain - Offset) 
 32mA
Specifications
FX
2NC
-4DA
Voltage output
Current output
Number of output points
4ch
Analog output range
-10V to +10V DC
(External load: 2k to 1M
Ω)
0mA to 20mA DC
4mA to 20mA DC
(External load: 500
Ω or less)
Offset
-5V to +5V
*1,*2
-20mA to +20mA
*1,*3
Gain
-4V to +15V
*1,*2
-16mA to +32mA
*1,*3
Digital input
With sign, 12 bits, binary
10 bits, binary
Resolution
*1
5mV(20V
×1/4000)
20
μA(20mA×1/1000)
Ov
eral
l ac
cura
cy Ambient temperature:
25
±5°C
±0.5%(±100mV) for 20V full scale
±0.5%(±100μA) for 20mA full scale
Same accuracy for 4mA to 20mA output
Ambient temperature:
0 to 55
°C
±1.0%(±200mV) for 20V full scale
±1.0%(±200μA) for 20mA full scale
Same accuracy for 4mA to 20mA output
Reference
Does not include any load fluctuation.
-
Time required for D/A 
conversion
2.1ms (The number of selected channels will not affect this value.)
Output characteristics
Insulation method
• The photocoupler is used to insulate the analog output area from the PLC.
• The DC/DC converter is used to insulate the power supply from the analog output.
• Channels are not insulated from each other.
Number of I/O points 
occupied
8 points (Taken from either the input or output points of the PLC.)
0
+10V
+2000
-2000
-10V
z
When the output mode is set to "0":
+2047
-204
8
z
When the output mode is "2":
(The dotted line is for mode 1.)
0
20mA
1000
Digital input
A
nal
o
g
out
pu
t
4mA
1023