4 Comparison of Performance Specifications
4.4 Temperature Sensor Input
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
Common Items
4.4 Temperature Sensor Input
4.4.6
FX
2N
-4AD-TC
Specifications
FX
2N
-4AD-TC
Centigrade(
°C)
Fahrenheit(
°F)
Number of input points
4ch
Input signal
Thermocouple type K or J
JIS C 1602-1995
Rated temperature range
• Type  K:  -100
°C to +1200°C
• Type J: -100
°C to +600°C
• Type  K:  -148
°F to +2192°F
• Type J: -148°F to +1112
°F
Digital output
• Type K: -1000 to +12000
• Type J: -1000 to +6000
• Type K: -1480 to +21920
• Type J: -1480 to +11120
Resolution
• Type K: 0.4
°C
• Type J: 0.3
°C
• Type K: 0.72
°F
• Type J: 0.54
°F
Overall accuracy
±(0.5% for full scale +1°C)
Time required for 
conversion
(240ms
±2%)× number of selected channels
Input characteristics
Insulation method
• The photocoupler is used to insulate the analog input area from the PLC.
• The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points 
occupied
8 points (Taken from either the input or output points of the PLC.)
0
+12000
(Type K)
+1200°C
(Type K)
-100°C
-1000
+600°C
(Type J)
+6000
(Type J)
Temperature
Di
gi
ta
l
out
put
0
+11120
(Type J)
+2192
°
F
(Type K)
-148
°
F
-1480
+21920
(Type K)
+1112
°
F
(Type J)
Temperature
Di
gi
ta
l
out
put