Mitsubishi Electronics MELSEC-F Manuel D’Utilisation

Page de 504
A-46
4 Comparison of Performance Specifications
4.4 Temperature Sensor Input
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
Common Items
4.4 Temperature Sensor Input
4.4.8
FX
2N
-2LC
*1.
For FX
2N
-2LC, the rated temperature range, digital output value, and resolution depend on the selected sensor
and mode.
*2.
Accuracy is not guaranteed for the temperature range of 0
°C to 399°C(0°F to 799°F) of the thermocouple -B input
and for the temperature range of 0°F to 32°F of the PL II and WRe5-26 inputs.
Specifications
FX
2N
-2LC
*1*2
Centigrade(
°C)
Fahrenheit(
°F)
Number of input points
2ch
Input signal
Thermocouple type K, J, R, S, E, T, B, N, PL II, WRe5-26, U, and L
JIS C 1602-1995
3-wire platinum resistance thermometer sensor(s)
Pt100 JIS C 1604-1997, JPt100 JIS C 1604-1981
Rated temperature range
Examples:
• Type K
-100
°C to +1300°C
• Type J
-100.0
°C to +800.0°C
Examples:
• Type  K
-100°F to +2400°F
• Type  J
-100°F to +2100°F
Digital output
Examples:
• Type K
-100 to +1300
• Type J
-1000 to +8000
Examples:
• Type  K
-100 to +2400
• Type  J
-100 to +2100
Resolution
1
°C or 0.1°C
1°F or 0.1°F
Ove
ral
l ac
curac
y
Ambient temperature: 
23
±5°C
±0.3°C(±1digit) for full scale
Ambient temperature: 
0 to 55
°C
±0.7°C (±1digit) for full scale
Cold junction temperature 
compensation error
±1.0°C
±2.0°C if the input value is in the range from -150°C to -100°C 
±3.0°C if the input value is in the range from -200°C to -150°C 
Time required for 
conversion
500ms(Sampling period)
Input characteristics
Insulation method
• The photocoupler is used to insulate the analog input area from the PLC.
• The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are insulated from each other.
Number of I/O points 
occupied
8 points (Taken from either the input or output points of the PLC.)
0
+1300
+1300
°C
-100°C
-100
Temperature
z
When type K (input mode 2)
 is set:
Di
gi
ta
l
out
put
0
+2400
+2400
°F
-100
°F
-100
Temperature
z
When type K (input mode 4)
 is set:
Di
gi
ta
l
ou
tput