Philips V200 Manuel D’Utilisation

Page de 328
Chapter 8
Operating Instructions
REF 1057983 A
Respironics V200 Ventilator Operator’s Manual
8-5
Alarm Status Indicators
The alarm status indicators located at the top of the ventilator alert you to the 
ventilator’s alarm conditions. (Refer to Chapter 9, “Alarms” for more detailed 
descriptions.)
Figure 8-4: Alarm Status Indicators
 
Alarm Status Indicators 
Alarm Indicator
Status
Description
Normal
Green
No active or auto reset alarm condition exists.
High
Flashing red
A high priority alarm condition exists.
Med/Low
Flashing 
yellow
Continuous 
yellow
A medium priority alarm condition exists.
A low priority alarm condition exists. In addition, 
indicates auto reset conditions
Vent Inop
Red (active)
The ventilator is not capable of supporting 
mechanical ventilation and requires service. 
During Vent Inop, the ventilator opens the safety 
valve to enable the patient to breathe room air 
spontaneously. The ventilator also discontinues 
detection of new alarm conditions during Vent 
Inop.
Safety Valve
Red (active)
The safety valve is open and the ventilator is not in 
operation. This is a high priority alarm condition
When the Safety Valve indicator is illuminated, the 
ventilator is not providing ventilatory support to 
the patient. The safety valve opens to allow the 
patient to breathe spontaneously through the 
ventilator circuit. The patient must be capable of 
creating a spontaneous breath in order to breathe 
through the safety valve.
Table 8-1: Alarm Status Indicators
Normal
Alarm Med/Low
Alarm High
VENT
INOP
SAFETY
VALVE