FieldServer FS-8700-20 Manuel D’Utilisation

Page de 22
FS-8700-20 Profibus DP Driver Manual 
 
 
 
 
 
Page 13 of 22 
 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldServer.com 
Tel: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldServer.com 
5. 
Configuring the FieldServer as a Profibus DP Slave Only 
The sections below describe the parameters available for configuring the driver as a Server. 
Note that * indicates an optional parameter, with the bold legal value being the default. 
5.1. General 
Section Title 
FieldServer 
Column Title 
Function 
Legal Values 
Title 
Provide a title for the 
configuration file (displays on 
RUI editor) 
Up to 15 alphanumeric 
characters 
System_Station_Address 
Profibus DP Slave Station ID of 
the FieldServer 
0-125 
 
Example: 
 
//  Common information 
 
FieldServer 
 
Title,  
System_Station_Address 
Profibus DP Slave, 
 
5.2. 
Data Arrays/ Descriptors 
Data Arrays are the neutral data buffers used by the FieldServer to pass data between 
communications drivers, and are defined as follows: 
 
Section Title 
Data_Arrays 
Column Title 
Function 
Legal Values 
Data_Array_Name 
Provide name for Data Array 
Up to 15 alphanumeric 
characters 
Data_Format 
Provides data format 
FLOAT, BIT, UInt16, 
SInt16, Packed_Bit, 
Byte, Packed_Byte, 
Swapped_Byte 
Data_Array_Length 
Number of Data Objects 
1-10,000 
 
Example 
 
//    Data Arrays 
 
 
Data_Arrays 
 
 
Data_Array_Name, 
Data_Format, 
Data_Array_Length 
DA_AI_01, 
UInt16, 
200 
DA_AO_01, 
UInt16, 
200