FieldServer FS-8700-20 Manuel D’Utilisation

Page de 22
FS-8700-20 Profibus DP Driver Manual 
 
 
 
 
 
Page 15 of 22 
 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldServer.com 
Tel: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldServer.com 
5.5. 
Server Side Map Descriptors 
Map Descriptors control when and how data is transferred to or from the card buffers for an external Profibus Master to access. 
Column Title 
Function 
Legal Values 
Map_Descriptor_Name 
Name of this Map Descriptor 
Up to 32 alphanumeric characters 
Data_Array_Name 
Name of Data Array where data is to be stored in 
the FieldServer 
One of the Data Array names from “Data Array” 
section above 
Data_Array_Offset 
Starting location in Data Array 
0 to maximum specified in “Data Array” section 
above 
Function 
Function of Server Map Descriptor 
RDBC, WRBC 
Node_Name 
Name of DP Server Node 
The node name specified in “Server Side Nodes” 
above 
Data_Type 
Data type 
FLOAT, WORD, BYTE, BIT 
DP_Buffer 
Specify buffer in the DP card being accessed. 
Input, Output 
Address 
Address in DP_Buffer being accessed, 
expressed in byte offset 
0-243 
Note: When using Data_Type BIT, the address is 
in bit eg. from 0 - 1951 
Length 
Number of points in DP_Buffer being accessed, 
expressed in points defined by Data_Type 
1- 1952, depending on Data_Type 
eg. when Data Type is WORD and length is 10, it 
means that 10*2 = 20 bytes are used in the buffer
Example 
 
//    Server Side Map Descriptors 
 
 
 
 
 
 
 
 
 
Map_Descriptors 
 
 
 
 
 
 
 
 
Map_Descriptor_Name, 
Data_Array_Name, 
Data_Array_Offset, 
Function,  Node_Name,  DP_Type,  DP_Buffer,  Address,  Length 
FLOAT_IN_01, 
DA_FI_01, 
0, 
RDBC, 
PDP_01, 
FLOAT, 
Output, 
0000, 
20 
INT_IN_01, 
DA_AI_01, 
0, 
RDBC, 
PDP_01, 
WORD, 
Output, 
0080, 
20     
BYTE_IN_01, 
DA_BI_01, 
0, 
RDBC, 
PDP_01, 
BYTE, 
Output, 
0120, 
20     
BIT_IN_0,1 
DA_DI_01, 
0, 
RDBC, 
PDP_01, 
BIT, 
Output, 
0140, 
32     
 
 
 
 
 
 
 
 
 
FLOAT_OUT_01, 
DA_FO_01, 
0, 
WRBC, 
PDP_01, 
FLOAT, 
Input, 
0000, 
20 
INT_OUT_01, 
DA_AO_01, 
0, 
WRBC, 
PDP_01, 
WORD, 
Input, 
0080, 
20     
BYTE_IN_01, 
DA_BO_01, 
0, 
WRBC, 
PDP_01, 
BYTE, 
Input, 
0120, 
20     
BIT_IN_01, 
DA_DO_01, 
0, 
WRBC, 
PDP_01, 
BIT, 
Input, 
0140, 
32