FieldServer FS-8700-20 Manuel D’Utilisation

Page de 22
FS-8700-20 Profibus DP Driver Manual 
 
 
 
 
 
Page 16 of 22 
 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldServer.com 
Tel: (408) 262-2299   Fax: (408) 262-9042   Toll_Free: 888-509-1970   email: support@fieldServer.com 
Appendix A. Special Driver Parameters 
Appendix A.1.  DP_Buffer 
Within the Profibus DP card, the FieldServer can access data from two distinct buffers.  The 
Input buffer is the data that is sent from the slave to master.  The Output buffer is the data 
sent from the master to the slave. Each Map Descriptor specifies which one of these buffers 
to access in the card. 
DP_Buffer 
Description 
Input 
Data to the master from a slave 
Output 
Data from the master to a slave 
 
Appendix A.2.  Data_Type, Address & Length 
Each Map Descriptor also specifies the Profibus DP data type. The data arrives from a 
Slave or is sent from a Master as a sequence of bytes.  By specifying the DP data type, the 
driver knows how to interpret the bytes within the buffer.  The supported types are Bit, Byte, 
Word and Float.  To indicate where in the buffer to access the data, the Address field is 
used.  For Byte, Word and Float type mappings, the address specifies the offset in bytes 
from the beginning of the buffer. For Bit type mappings, the address specifies the offset in 
bits from the beginning of the buffer.  A bit offset of 0 would access the least significant bit in 
the first byte in the designated buffer. 
Data_Type 
Description 
Bit 
Transfer Length bits to Data Array 
Byte 
Transfer Length bytes to Data Array 
Word 
Swap the bytes and transfer Length words to Data Array 
Float 
Swap the bytes and transfer Length floats to Data Array