DiaGNostic tEsts
Page 125
B.   pe r fo r m   a   l o a d   t e s t   o n   t h e   B a t t e r y : 
(maintenance Free Battery)
1.  Using  a  lead  acid  battery  load  tester  test  the  load 
capability of the battery. 
2.  Follow the load tester’s manufacturer’s instructions carefully.
Figure 3. A Typical Battery Load Tester
c.   t e s t   B a t t e r y   S t a t e   o f   c h a r g e : 
(non-maintenance Free Battery)
1.  Use  an  automotive  type  battery  hydrometer  to  test 
battery state of charge.
2.  Follow  the  hydrometer  manufacturer’s  instructions 
carefully.  Read  the  specific  gravity  of  the  electrolyte 
fluid in all battery cells.
3.  If cells are low, distilled water can be added to refill cell 
compartment.
4.  If the hydrometer does not have a “percentage of charge” 
scale, compare the reading obtained to the following:
a.  An  average  reading  of  1.260  indicates  the 
battery is 100% charged.
b.  An average reading of 1.230 means the battery 
is 75% charged. 
c.  An average reading of 1.200 means the battery 
is 50% charged. 
d.  An  average  reading  of  1.170  indicates  the  bat-
tery is 25% charged. 
CHECK EACH CELL
AFTER CHARGING
USE A TEMPERATURE 
COMPENSATED
HYDROMETER
Figure 4. Using a Battery Hydrometer
5.  Test Battery Condition:
a.  If the difference between the highest and lowest 
reading  cells  is  greater  than  0.050  (50  points), 
battery  condition  has  deteriorated  and  the  bat-
tery should be replaced. 
b.  However,  if  the  highest  reading  cell  has  a 
specific  gravity  of  less  than  1.230,  the  test 
for  condition  is  questionable.  Recharge  the 
battery to a 100 percent state of charge, and 
then repeat the test for condition. 
RESULTS:
1.  Remove  the  battery  and  recharge  with  an  automotive 
battery charger, if necessary. 
2.  If  battery  condition  is  bad,  replace  with  a  new  battery.
LIQUID 
LEVEL
1220
1230
1240
1250
1260
1270
80°
0
4
8
12
16
20
24
28
32
4
8
12
16
20
24
28
32
26.6°
 
Cell #  
Specific Gravity
 
1.255
 
1.260
 
1.235
 
1.250
 
1.240
 
1.225
HIGH READING
LOW READING
35 POINTS DIFFERENCE
Figure 5. Reading a Battery Hydrometer
DC CONTROL
Part 4