If control is in Cool mode, and Set Point is selected as the 
Cut Out: 
Temperature
Operating
 
Setpoint 
 
+ 
Differential
Range 
  Temperature  (plus) 
Example:
 
 This control is a temperature control and is not to 
be used as a temperature limit control.
 
To prevent scald injury, do not use this control to 
heat water for bathing, washing, hot tub or similar 
applications.
The factory default setpoint for this control is 45°F (7°C) for 
Cool and 120°F (49°C) for Heat. Setpoint temperature can 
be adjusted using the 
 or   keys. A power loss does not 
lose the settings. All menu item selections and setpoint set-
ting are stored in a permanent memory.
The user determines the temperature operating range. To 
determine the temperature range, the user must select the 
Set Point (SP) as the Cut Out or Cut In temperature, Dif-
ferential (dFF) and enter a set point temperature. Cut out 
is when the load is turned off and cut in is when the load is 
turned on.
NOTE: The Heat/ Cool switch (SW1) MUST be in the proper 
position BEFORE setting options. 
COOL/REFRIGERATION
To use as a Cooling control, SW1 must be set to Cool. The 
snowflake ( ) icon will display.
If control is in Cool mode, and Set Point is selected as the 
Cut In:
Temperature
Operating        =     Setpoint 
     –            Differential
Range   
Temperature 
(minus) 
Example:
40° Setpoint (Cut In)
35°
SW1 = Cool
Set Point (SP) = Cut In
Differential = 5
Setpoint temperature = 40°
Te
mperature Range
40° Setpoint (Cut Out)
45°
SW1 = Cool
Set Point (SP) = Cut Out
Differential = 5
Setpoint temperature = 40°
Te
mperature Range
HEAT
To use as a Heating control, SW1 must be set to Heat. The 
flame ( ) icon will display. 
If control is in Heat mode, and Set Point is selected as the 
Cut Out:
Temperature
Operating
 
Setpoint 
 
 
Differential
Range 
  Temperature  (minus)
 
Example:   
If control is in Heat mode, and Set Point is selected as the 
Cut In:
Temperature
Operating
 
Setpoint 
 
+ 
Differential
Range 
  Temperature  (plus) 
Example:
100° Setpoint (Cut Out)
95°
SW1 = Heat
Set Point (SP) = Cut Out
Differential = 5
Setpoint temperature = 100°
Te
mperature Range
100° Setpoint (Cut In)
105°
SW1 = Heat
Set Point (SP) = Cut In
Differential = 5
Setpoint temperature = 100°
empera
ture
an
e
Menu
Item
Description
Factory
Default
Options
Press   or 
to select
Comments
bIn
Binary Input
Off
On or Off
The default setting of Off will have no affect on the 
operation of the thermostat. When set to On, it allows 
an external binary input (switch or relay) to start a tem-
perature set back. See Set Back (Sb).
Sb
Set Back
0
0 to 50
Selects the number of degrees the thermostat will 
change the setpoint temperature when the external 
binary input signal is received. 0 will cause no tempera-
ture change to occur. See Binary Input (bin).
AL
Alarm
0
0 to 99
Selects the time delay (in minutes) before a Tempera-
ture Out of Range alarm output is sent.
A setting of 0 disables the alarm relay.  
USER MENU 
OPERATION