Lock Panel (LP)
The keypad can be locked to prevent unwanted tampering 
with the control settings. In the User Menu, change the menu 
item LP selection to On. When the menu is exited and set-
tings are stored, the   or  , and 
 keys will be disabled 
from normal use.
To unlock the keypad, press and hold 
 for 5 seconds. 
The display will change to show LP On. Momentarily press  
 or   to change to Off and then momentarily press 
.     
The control will return to normal operation and the keypad 
will be unlocked.
Binary Input (bIn) and Set Back (Sb)
Binary Input is an option to allow the setpoint temperature 
to set back to conserve energy or for other reasons as 
determined by the user. Set Back determines the number of 
degrees the setpoint temperature will be changed.
An external switch or N.O. relay can be connected to the BIN 
and GND terminals of the control. With bIn set to On, when 
the switch is closed, the control will change the setpoint tem-
perature by the number of degrees set in Sb. In Heat mode, 
setpoint temperature will change lower or cooler. In Cool 
mode, setpoint temperature will change higher or warmer. 
During the time that the switch is closed, bIn will appear in 
the lower left corner of the display. If an alarm is connected 
be sure that the alarm delay time is set long enough to allow 
for the temperature change to avoid a “false” alarm.
Alarm (AL)
This control has an alarm relay that will provide an output to 
alert of a malfunction. The alarm relay output must be con-
nected to an external light, audible alarm or other device as 
needed by the user. If AL is set to 0, the alarm relay will not 
provide any alarm output. If AL is set to a value greater than 
0, the alarm relay output provides indication of three error 
conditions: Temperature Out of Range, Power Loss and Sen-
sor Operation Failure. Although AL must be set to a value 
greater than 0 for any alarm output to be provided, the value 
selected is the time delay, in minutes, before a Temperature 
Out of Range alarm is set. The alarm time delay does not 
apply to Power Loss or Sensor Operation Failure.
OPERATION 
Temperature out of range – If the temperature is more than 
5° from the setpoint, continuously for the length of time set in 
AL, the alarm relay output will close. The delay should be set 
to allow for conditions that will cause the temperature to vary, 
such as defrost cycle, opening door for stock removal or 
replacement or Set Back changes. When setting the AL time, 
consideration should be given to these events to prevent a 
false alarm.
If the control set back feature is used to change the setpoint, 
the delay period set in AL should consider the time it takes 
for the system to reach the set back temperature to avoid a 
false alarm.
Power Loss – If the temperature control experiences an input 
power failure, the control will close the alarm relay before 
total power of the control is lost. The delay time is not used in 
this event, and the alarm relay will close within seconds of a 
power failure. In addition, the load relay contact change state 
per the Sensor Operation Failure (SOF) setting.
When power returns, the alarm contacts will open. The load 
relay will remain in the SOF position the length of time set in 
Anti Short-Cycle Delay (ASd) after power resumption. The 
display will blink the flame or snowflake icon for this time to 
indicate the load is “locked” out. This is to help protect the 
user’s equipment from damage by short cycle switching.
Sensor Operation Failure (SOF) – If in operation, the sen-
sor wiring should become open or shorted, the temperature 
control will begin blinking SOF with SH for shorted or SO for 
sensor open. However, the control will wait approximately 
1 minute before closing the alarm output relay - indicating 
sensor operation failure. If during the 1 minute, the sensor 
“resumes” normal operation, the time is reset and the control 
returns to normal display. The load relay will operate as se-
lected in sensor operation failure (SOF).
Multiple Sensors
The 16E09 is normally operated with one sensor. If an aver-
age temperature of an area is required, 4 sensors may be 
used and wired in the method shown below. If 4 sensors are 
used, they must all be of the same model. 
NOTE: When using multiple sensors, 4 sensors must be 
used. The control will not operate with 2 or 3 sensors.
Using  the  Alarm  Output  and  power 
stealing  in  combination  –  When  using 
power stealing mode and the alarm output, it is 
important for the installer to review the wiring circuit 
of the installation to insure no device is present that could 
interrupt electrical power to the temperature control.  Such 
a device could be a defrost timer, as one example, that may 
be used in some refrigeration applications.
If  a  device  is  in  the  system  wiring  that  can  periodically 
disrupt  power  to  the  load  and  the  temperature  control, 
the power stealing mode of the control cannot be used. A 
neutral wire must be connected to the control and select 
the non power stealing mode for the control. This keeps 
power to the control during power interruptions to the load 
and avoids a “false” alarm output.