Heat & Glo  •  VRTIKL-CE  •  7031-292 Rev E  •  12/07
4
Termination Locations
A. Flue Termination Minimum Clearances
Figure 4.2   Multiple Vertical Termination
Figure 4.1  Termination Clearances
Figure 4.3 specifi es  minimum  fl ue heights for various 
pitched roofs.
Figure 4.3   Minimum Height from Roof to Lowest Discharge
                     Opening
Measure vertical clearances from this surface.
Measure horizontal clearances from this surface.
(See Figure 4.4 for specifi c clearances.)
Fire Risk.
Explosion Risk.
Maintain fl ue clearance to combustibles 
as specifi ed.
WARNING
•  Do not pack air space with insulation or 
other materials.
Failure to keep insulation or other materials 
away from fl ue pipe may cause fi re.
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
Roof Pitch 
H (Min.) M
Flat to 6/12..............................................................30*
Over 6/12 to 7/12 ....................................................38*
Over 7/12 to 8/12 ....................................................46*
Over 8/12 to 9/12 ....................................................61*
Over 9/12 to 10/12 ..................................................76
Over 10/12 to 11/12 ................................................99
Over 11/12 to 12/12 .............................................1.22
Over 12/12 to 14/12 .............................................1.52
Over 14/12 to 16/12 .............................................1.83
Over 16/12 to 18/12 .............................................2.13
Over 18/12 to 20/12 .............................................2.29
Over 20/12 to 21/12 .............................................2.44
*.91M minimum in snow regions
Gas Termination
Wood & Fuel Oil Termination
A
15 cm
51 cm
61cm
(MINIMUM) TO
PERPENDICULAR
WALL
(GAS ON LY)
GAS
TERMIN ATION
GAS, WOOD OR FUEL
OIL TERMINATION