5. 1 Fault Mode Troubleshooting Guide
5.2  Additional Troubleshooting
LED Pad Display
Drive Status/Fault Indication
Actions Required
Blank Display
Drive not powered
Check for drive input power
Display unplugged or failed
Check display plug connection
0019 - 0600
Numeric display shows Pump RPM, indicates motor running
rdY
Drive Ready (Enabled & Not Running)
In AUTO mode, make sure AUTO-RUN contact is closed 
between pins 5 & 6 of 6-pin connector if pump should be 
running
inh
Drive Inhibited (Not Enabled)
Install jumper between IntelliGear terminals 11-12
tr01
Motor thermostat trip - Overtemp
Check motor thermostat connections between IntelliGear 
terminals 5 & 9  
(Install jumper if motor has no thermostat wires -P1/P2)
Check motor fan & clean debris or obstruction to air flow
Check for motor overload
tr02
Internal brake resistor trip - Overtemp
Contact factory
tr03
Pump RUN DRY or HIGH PRESSURE fault trip
Check for proper flow and pressure in pump
UU
DC Bus Undervoltage
Check incoming power for voltage level too low
OU
DC Bus Overvoltage
Check incoming power for voltage level too high
Check for over-running load (pressure over-driving pump)
Adjust drive parameter 04 (deceleration time) to a higher 
setting using drive keypad/display
ph.AC
Loss of a motor phase
Check motor connections at IntelliGear grey terminal strip
OI.AC
Overcurrent at Drive Output
Check motor connections at IntelliGear grey terminal strip
Check for ground fault or line-line fault in motor wiring
Check for moisture or insulation damage in motor windings
It.AC
Motor Overload (I X t)
Check for excessive torque load at pump
Oht1
Overheating in Output Transistors
Check heatsink fins for debris or obstruction to air flow
Provide supply of cool air if ambient exceeds 40°C
Reduce torque load from pump
Oht2
Overheating in Brake Transistor
Adjust drive parameter 04 (deceleration time) to a higher 
setting using drive keypad/display
Reduce start/stop frequency
rS
Stator Resistance Measurement Fault
Check motor connections at IntelliGear grey terminal strip
SCL
Serial connection between keypad and drive broken
Check display plug connection
EEF
EEPROM fault in drive
Contact factory
OI.br
Overcurrent at Brake Transistor
Contact factory
Symptom
Probable Cause(s)
Actions Required
Not Running, No Fault 
Indication on Display
Drive not in HAND or AUTO mode
Press HAND or AUTO button on Keypad
Drive in AUTO mode, but AUTO-RUN contact not 
closed
Close AUTO-RUN contact or 
Jumper pins 5-6 on 6-pin connector cable
Unit Runs Only at Low 
Speed in AUTO mode
4-20 mA signal is not present
Connect 4-20 mA signal  and Verify that the signal 
current is present  (pins 1 & 2 of 6-pin connector)
4-20 mA signal polarity is reversed
Verify current enters pin 1 of 6-pin connector  Reverse 
the connections if necessary
In AUTO, Unit Does 
Not Achieve Maximum 
Output RPM at 20 mA 
Signal Input
4-20 mA signal not achieving full 20 mA at maximum 
speed reference
Signal source may not be capable of producing 20 
mA with the drive input impedence of 500 ohms - 
must be able to produce at least 10 VDC at pin #1 of 
6-pin connector cable
Maximum speed setting of operator keypad setting is 
not set to 100%
Press UP ARROW on keypad until maximum speed 
is attained
IntelliGear MAXIMUM SPEED setting has been turned 
down
Adjust drive parameter 02 to 2700 RPM using drive 
keypad/display