1.5 - Description of cables and protection devices (Customer Supplied)
NOTICE: When using a circuit-breaker, it must be a motor circuit-breaker (D curve).
•  Comply with the size of protection fuses.
•  The cable size may vary according to legislation applicable in the country, which will take precedence over the values
given in the table below without exception. 
1.6 - UL conformity
1.6.1 Specified mains supply
The drive can be incorporated in an installation with short circuit capacity of 5000 A rms maximum at voltage 264 VAC rms 
maximum for 230 V (TL) drives or 528 VAC rms maximum for 400 V (T) drives.
1.6.2 Cables
Only class 1 copper cables 60/70° C (140/167° F) should be used.
1.6.3 Fuses
UL conformity is adhered to if the fuses are UL-listed, fast-blow fuses (class CC up to 30 A) with a rating as indicated in 
the above table and if the short-circuit symmetrical current does not exceed 5 kA.
1.4 - Radio-frequency interference:
1.4.1 - General
Variable speed drives use high-speed switches (transistors, 
semi-conductors) which switch high voltages (around 660V 
for 3-phase drives) at high frequencies (several kHz). This 
provides better efficiency and a low level of motor noise. As 
a result, they generate radio-frequency signals which may 
disturb operation of other equipment or distort measurements 
taken by sensors:
• due to high frequency leakage currents which escape to
ground via the stray capacity of the drive/motor cable and 
that of the motor via the metal structures which support 
the motor
• by conduction or feedback of R.F. signals on the power
supply cable; conducted emissions
• by direct radiation near to the main supply power cable
or the drive/motor cable: radiated emissions
These phenomena are of direct interest to the user. The 
frequency range concerned (radio-frequency) does not affect 
the energy distribution company.
1.4.2 - Standards (Emission)
The maximum emission level is set by (EN 50081-2) and  
(EN 50081-1). IntelliGear Plus conforms to:
• EN 50081-2 as standard
• EN 50081-1 with filter option
1.4.3 - Standards (Immunity)
The maximum immunity level is set by (EN 50082-2) and 
(EN 50082-1). IntelliGear Plus conforms to: 
• EN 50082-2 and EN 50082-1 as standard
Motor 
115V Single Phase Power Supply
230V Single Phase Power Supply
HP Rating
IntelliGear 
Plus Number
Input Amps Wire Gauge
Fuse Size
IntelliGear 
Plus Number
Input Amps Wire Gauge Fuse Size
0.50
I 310M 050
5
14AWG
10 A
I 31M 050
2.5 
14AWG
8A