Emerson BW1 Manuel D’Utilisation

Page de 15
IntelliGear Plus Variable Speed MD Gearmotors
7
2 - Installation
After connection, ensure that the seals are firmly in place, 
and that the screws and cable glands are watertight to ensure 
drive protection. Clear any condensation from the drain holes 
at the bottom of the motor.  
2.1 - General
The IntelliGear Plus is usually fitted to the gear and mounted 
to the machine with flange or foot mounting. The motor fan 
cools the whole assembly. Make sure that the ventilation air 
inlet is free of obstruction. 
3 - Connections
Connection with copper conductor only.
3.1 - Control Terminal Blocks
Remove the terminal block from it’s fixed holder 
(unplugged) before making any connections, to avoid 
putting pressure on the card.
CAUTION:  The IntelliGear Plus has a positive logic 
configuration. Using a drive with a control system which 
has a different control logic may cause unwanted starting 
of the motor.
The control circuits in the drive are isolated from the 
power circuits by single insulation (IEC 664-1).
The installer must ensure that the external control 
circuits are isolated against any human contact.
If the control circuits need to be connected to circuits 
conforming to SELV safety requirements, additional 
insulation must be inserted to maintain the SELV 
classification.
Removable screws in terminal block:
Tightening torque = 2.62 in. lbs.
Maximum cross section = 17 AWG
3.2 
Power terminal blocks
3.2.1  Terminal block for power supply PB1
 
(marked L&N)
 
This terminal block is used to connect the 3 phase
 
power supply when the RFI filter is not used in an
 
IntelliGear Plus. Otherwise, the RFI filter output    
 
is screwed onto this connector and the power  
 
 
supply should be attached to the terminals located  
 
on top of the filter. (See table below)
Screw terminal blocks
310M & 31M
Tightening Torque
7.1 in. lbs.
Max. cross-section
AWG 14
Numbered Controller 
Terminal Blocks
Terminal Block
for Power Supply