Impinger I -–1000 Series Service Manual - Domestic 
SEQUENCE OF OPERATIONS 1000/1001/1004/1005/1200/1201/1204/1205 
MODEL 1000 - 120/230 VAC - 60HZ - NATURAL GAS 
MODEL 1001 - 120/230 VAC - 60HZ - L.P. GAS 
MODEL 1004 - 120/230 VAC - 60HZ - NATURAL GAS 
MODEL 1005 - 120/230 VAC - 60HZ - L.P. GAS 
MODEL 1200 - 120/230 VAC - 60HZ - NATURAL GAS/DUAL BELT 
MODEL 1201 - 120/230 VAC - 60HZ - L.P. GAS/DUAL BELT 
MODEL 1204 - 120/230 VAC - 60HZ - NATURAL GAS/DUAL BELT 
MODEL 1205 - 120/230 VAC - 60HZ L.P.GAS/DUAL BELT 
 
POWER SUPPLY 
Electrical Power to be supplied to the Oven by a four conductor service. . Voltage 
from the black conductor to the white conductor is 120 VAC. 
Black conductor is Hot 
Red conductor is Hot 
White conductor is Dedicated Neutral 
Green conductor is Ground 
CONTROL BOX AUTO 
COOL DOWN 
When  the  temperature  in  the  Control  Box  reaches  120°F  +  3°,  the  Cooling  Fan 
Thermostat  will  switch  power  to  the  Control  Box  Cooling  Fan.  The  Thermostat  will 
interrupt power to the Cooling Fan when the Control Box temperature falls to 100°F + 
3°. 
 
MAIN FAN CIRCUIT 
Electrical power is permanently supplied to the normally open contacts of the Double 
Pole  Main  Fan  Relay,  the  Cooling  Fan  Thermostat,  the  normally  open  Main  Fan 
Switch, and the normally open Cool Down Thermostat (thermostat closes at 160°F 
and opens at 140°F). Closing the Main Fan Switch energizes the coil of the Relay. 
The normally open contacts now close, energizing the Main Fan Motor through (2) 
10A fuses, and the Cooling Fan. Closing the Fan Switch also supplies power to the 
Hour Meter (hour meter discontinued after S/N 3484), the 12.6 VAC Transformer, the 
Burner and Conveyor Switches. 
TRANSFORMER (12.6 
VAC) 
Upon closure of the Fan Switch, 120 VAC is supplied to the primary of the 12.6 VAC 
Transformer. The Transformer steps the voltage down to 12.6 VAC (normally 13 to 
14  VAC)  with  a  center  tap,  and  supplies  power  to  the  Time/Temp  Display.  The 
voltage  from  each  leg  of  the  Transformer's  secondary  to  the  center  tap  should  be 
one half of the secondary voltage. 
BURNER CIRCUIT 
Closing  the  Fan  Switch  and  the  normally  open  Burner  Switch  supplies  120  VAC 
through the Air Pressure Switch, to the normally open contacts of the Burner Motor 
Relay,  and  the  primary  of  the  24  VAC  Step  Down  Transformer.  The  Transformer 
secondary  supplies  24  VAC  (through  a  1A  fuse  on  Model  1004  and  1005)  to  the 
Relay Coil (the normally open contacts close within  30 seconds), and the normally 
open Centrifugal Switch. When the Relay contacts close, the Burner Blower Motor is 
energized. As this motor reaches approximately1600 R.P.M., its internal centrifugal 
switch closes, supplying  24 VAC to the Gas Control Valve. When the Gas Control 
Valve is supplied with 24 VAC the pilot valve is energized, and the ignitor circuit is 
energized. Ignition should now occur. After pilot flame is proven, the main gas valve 
is energized. The Burner Indicator Light is also energized. 
CONVEYOR DRIVE(S/N 
100 to 4389) 
Closing the Fan Switch and the normally open Conveyor Switch supplies 120 VAC 
through a 3A Fuse, to the Motor Control Board. AC volts are converted to D.C. volts 
and  are  supplied  to  the  Conveyor  motor  at  board  terminals  A1  and  A2  through  a 
D.P.D.T.  Reversing  Switch.  Adjustment  of  the  Speed  Control  Potentiometer  (500 
ohm, 10 turn)  will change  resistance  at terminals S1, S2, and  S3 varying the D.C. 
voltage to the motor. The speed of the Conveyor Motor will increase or decrease as 
the D.C. voltage from the Motor Control Board increases or decreases respectively. 
(S/N 4390 and UP) 
Closing the fan switch and the normally open conveyor switch supplies 120 VAC to 
the Motor Control Board. AC volts are converted to DC volts and are supplied to the 
Conveyor  Motor  at  terminals  A+  and  A-.  Adjustment  of  the  Speed  Control 
Potentiometer (5,000 ohm 10 turn ) will change resistance at terminals P1, P2, and 
P3  varying  the  DC  voltage  to  the  motor.  The  speed  of  the  conveyor  motor  will 
increase  or  decrease  as  the  DC  voltage  from  the  board  increases  or  decreases 
respectively.  As  the  motor  turns,  it  drives  both  the  reducer  gearbox  and  the  tach.