  In the full mode (3 drops in the display) the Y2 valve will be energized
continuously.
h
  When the timer counts to 0 or the core temp probe (B10) reaches the set amount
the cycle ends and the steam generator reverts to the standby temperature of 190-
degree F.
6
  With the combi in the Rethermalization mode with time on the timer, the door closed
and the start switch is depressed
a
  The front display will include a lighted bar under the Retherm symbol
  When the heat circuit is energized the heat symbol will be energized
  The cooking mode symbol will be energized.
  The time display will invert and begin to count down.
b
  The fan circuit is energized by the Control Board (A10) transmitting and
receiving a signal from terminals 5,6,7 and 8 on connector X10 to terminals 3,4,5
and 6 of connector X28 on the Gas Board (A20)
c
  The Gas board (A20) Transmits a signal from terminal 4 of connector X26 to the
Motor Drive.
  The motor Drive Board sends a signal through the thermal switch in the motor
from Terminal 5 and receives on terminal 6 
  If the thermal switch is not open the Motor Drive Board (U10) sends 220
VAC 3 phase to the motor.
  The motor reverses direction every 120 seconds with a 15 second coast.
  NOTE: If the set temperature is less than 212 degrees F than fan will be
pulsed on for 2 seconds every 60 seconds after the cabinet set temp (B6).
d
  The steam generator heat circuit is energized. Steam production takes precedence
in the Combi mode
  A signal is sent from terminal 8 of connector X24 on the Gas Board (A20) to
terminal 4 of connector X2 on the Steam Power Burner and Fan Control
(U21) selecting the set speed of the combustion blower.
  When this speed is attained the signal is sent from terminal 2 of connector
X2 on the Steam Power Burner and Fan Control (U21) to terminal 9 of
connector X24 on the Gas Board (A20)
  A request for heat is sent from terminal 3 of connector X21 on the Gas Board
(A20) to terminal 10 on connector X1 on the Steam Burner Control Module
(N21)
  24 VAC is sent from terminal 2 of connector X2 on the Steam Burner
Control Module (N21) to the hot surface igniter (R20).
  The gas valve is energized allowing gas and air into the burner chamber to
be ignited by the hot surface igniter.
  The Steam Burner Control Module (N21) senses at least 1.5 micro amps
DC from the flame sensor (P1) at terminal 3 of connector X2 and sends a
signal from terminal 2 of connector X1 to terminal 11 of connector X25
on the Gas Board (A20)
e
  After the bypass probe (B5) is satisfied then the hot air heat circuit is energized to
increase the cabinet temperature to the setting.