Hussmann proto-aire Manuel De Montage

Page de 124
Protocol™ Installation and 
Service Manual 
Dimensions and Weights 
 
Vertical L 
Weight 
Nomenclature 
(in.) (in.) (in.) (lb) 
17FR 
30.5 80  30.5 1200 
18FR 
43.5 80  30.5 1500 
 
Horizontal L 
Weight 
Nomenclature 
(in.) (in.) (in.) (lb) 
20FR, 13FR, 29ZX 
122 
32 
30.5 
1700 
32FX, 33FX, 34FX 
122 
32 
30.5 
1900 
 
Proto-Aire™ L 
Weight 
Nomenclature 
(in.) (in.) (in.) (lb) 
3 & 4 fan 
128 
56.5 
42 
2800 
6 fan (super) 
185 
56.5 
42 
3700 
 
Note: Maximum weight includes sound coating and refrigerant. 
 
Receiver Capacities are based on 80% liquid fill at 105 °F. 
 
Vertical – 55 lb 
Horizontal– 72 lb  (Standard)  
 
 
200# option 
3 & 4 Fan Proto-Aire™ - 72 lb  (Standard)   
200# option 
6 Fan Proto-Aire™ - 145 lb  (Standard) 
 
200# option 
 
 
Field Supplied and Installed Water Components
 
 
The Protocol™ comes equipped with a flow control/shutoff valve for servicing the plate 
heat exchanger.  All other water loop components must be field supplied and installed.  A 
16-20 mesh strainer (1 mm) is required immediately upstream of each Protocol™. 
 
Accessibility 
 
All Standard Control Panel Doors require 40 inches clearance.  Oversized Control Panel 
Doors require 48 inches clearance.  Vertical Protocol™ units must be serviceable from the 
front and top of the unit.  Access to either side is also recommended.  Horizontal 
Protocol™ units must be serviceable from three sides, the front and right side as well as the 
top or back as viewed facing the removable panels.  A minimum of 40 inches clearance is 
recommended. 
 