Toshiba reliability in motion 1700 Manuel D’Utilisation

Page de 39
TOSHIBA 
 
29 
Appendix A:  Specifications 
Model Number 
UF1A1A020C6RK 
UF1A1A024C6RK 
Capacity 
2000VA (1.40KW) 
2400VA (1.68KW) 
Input voltage
1
 
Single phase 120VAC, +20% to -50% 
Input frequency 
30 to 70 Hz 
Input capacity 
2000VA 
2400VA 
Input 
Input power factor 
Approximately unity (0.95 to 1.0) 
Input voltage
2
 
Single phase 120VAC, ±10% 
Output voltage 
Single phase 120VAC 
Bypass 
Overload rating 
See appendix C 
Output voltage 
Single phase 120VAC 
Output voltage regulation 
Within +/- 3%, steady state 
Output frequency 
50/60 Hz 
(+/- 0.5% in free running mode, line sync 
range +/-1Hz)
 
Rated load power factor 
0.7 
Rated output current (rms) 
16.7A 
20A 
Inverter overload capacity 
125% for one minute; 150% for 30 seconds 
Output 
Crest factor 
2.5 at full load 
Type 
12V, flame retardant, 
valve regulated lead acid 
Battery backup time 
(fully 
charged, 0.7 power factor, 25°C (77°F)
 
10 minutes 
(at full load)
 
7 minutes 
(at full load)
 
Battery 
Configuration 
2 strings in parallel, 4 batteries per string 
Operating temperature 
0° to 40°C (32° to 104°F) 
Altitude 
Up to 1000m (3000 ft) above sea level 
Efficiency 86% 
Environment 
Operating Humidity 
30 to 90%, non-condensing 
 
Note1:  Below 77% input voltage unit may begin parallel operation; supplementing input 
power with battery power.  The point at which parallel operation begins is load 
dependant (for a detailed explanation of Parallel Operation see appendix D). 
 
Note2:  Input voltage range is limited in bypass for load protection.  (For a detailed 
explanation of Bypass Undervoltage / Overvoltage see appendix E.)