Air-Cooled Models—Self-Contained Compressor
25
Liebert
®
 Challenger 3000
Figure 14 Air-cooled condensers
Table 4
Air-cooled condenser statistics
Model 
Number
of Fans 
Connection Sizes
(OD Copper)
Net Weight
lb (kg)
“A” Dimension
in (mm)
Hot Gas (in.) 
Liquid (in.) 
083
1
7/8
5/8
295 (133.8)
42 (1067)
104
1
1-1/8
5/8
315 (142.8)
42 (1067)
165
2
1-1/8
7/8
425 (193)
82 (2083)
Secure each leg to condenser frame at all 
points shown using hardware provided.
Liquid line
* B
TYPICAL FOOTPRINT
Liebert Lee-Temp
 heater 
pad connection box
*B - Inverted traps are to be field-supplied and installed 
(typ). When installing traps, provide clearance for swing 
end of access door. Traps are to extend above base of 
coil by a minimum of 7-1/2" (190mm)
Liquid line
Hot gas line
Electric service 
supplied by
others
Electric
service
supplied by 
others
Hot gas 
line
* B
LIEBERT LEE-TEMP CONDENSER
FAN SPEED AND VFD CONDENSER
44"
(1118mm)
18" (457.2mm)
43-9/16"
(1106mm)
51-7/16"
(1306.5mm)
37-7/8"
(962mm)
Common to all models. See Table 4 
below for key to “A” dimension.
CONDENSER MOUNTING
1"
(25.4mm)
1-3/4"
(44.5mm)
4-1/4"
(108mm)
4-1/4"
(108mm)
1-3/4"
(44.5mm)
1"
(25.4mm)
1-3/4"
(44.5mm)
1" typ.
(25.4mm)
1-3/4"
(44.5mm)
37-11/16"
(957.3mm)
1-3/4"
(44.5mm)
A
9/16" (14.3mm)
diameter holes
8 places for
1/2" (12.7mm)
diameter bolts
43-3/16"
(1097mm)
SINGLE FAN AIR-COOLED CONDENSERS
1" typ.
(25.4mm)